| Notes |
| Date |
Text |
| 2007-11-27 09:47:42 | DENIED; | | | COMMENTS FROM LAST REVIEW 1 THRU 8 OK MEANS COMMENT WAS | | | ADDRESSED NO MEANS NOT ADDRESSED. | | | 1. OK | | | 2. NO; GREASE TRAP WILL BE SIZED BY THE CITY OF WPB | | | UTILITYDEPARTMENT BEFORE PLANS ARE APPROVED BY THE | | | PLAN REVIEW ( PLUMBING). | | | 3. NO; 3 COMPARTMENT SINK ISSHOWN ON SANITARY RISER | | | DIAGRAM DIRECTLY TIDE INTO THE SANITARY SYSTEM. | | | 4. OK | | | 5. NO; CAN WASH WASTE IS SHOWN GOING TO SANITARY (GOOD) | | | BUT AS DRAWN DRAN DOES NOT GO THRU GREASE TRAP AS | | | REQUIRED. | | | 6. YES, NO; NOTE ADDED BUT MOP SINK NOT VENTED AS | | | DRAWN. | | | 7. YES, NO; THE BACKFLOW PERVENTOR FOR THE SHOPPING | | | CENTER IS FOR THE CITY'S PROTECTION. A RPZ IS REQUIRED | | | FOR THE RESTAURANT FOR ADDITIONAL PROTECTION. | | | 8. NO; PIPE SIZING IS NOT COMPLETE ON RISER DIAGRAM. | | | NEW COMMENTS | | | 9. BATHROOM LAVATORY NOT SHOWN ON RISER DIAGRAM. | | | 10. WATER RISER DIAGRAM; GAVANIZED PIPE IS NOT A COMMON | | | USED WATER PIPING MATERIAL. COPPER OR CPVC ARE USED IN | | | THIS AREA. | | | 11. GAS RISER ADDED TO PLANS SEE COMMENTS UNDER THE GAS | | | STOP. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|