| 2007-11-09 14:35:14 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST |
| | PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| | (F.S.). |
| | |
| | *** DENIED *** |
| | 1) BE ADVISED MOST SHEETS IN ONE SET OF PLANS HAVE NOT |
| | BEEN SIGNED AND SEALED BUT ARE COPIES THESE ARE NOT |
| | ACCEPTABLE, SEE FAC 61G15-23.002. PLEASE CORRECT. |
| | |
| | 2) PLANS PAGE A-1 SHOWS THE HOOD EXHAUST DUCT AS |
| | 24"X24" IF THE EXHAUST FAN IS 3000 CFM'S THAT WOULD PUT |
| | THE AIR VELOCITY AT 750 FPM. PER 2004 FBC/M 506.3.4 AIR |
| | VELOCITY. |
| | GREASE DUCT SYSTEMS SERVING A TYPE I HOOD SHALL BE |
| | DESIGNED AND INSTALLED SO AS TO PROVIDE AN AIR VELOCITY |
| | WITHIN THE DUCT SYSTEM OF NOT LESS THAN 1,500 FEET PER |
| | MINUTE AND NOT GREATER THAN 2,500 FEET PER MINUTE. |
| | PLEASE CORRECT. |
| | |
| | 3) IF THE HOOD IS U.L. APPROVED THEN PUT THE U.L. |
| | APPROVAL NUMBER ON THE PLAN. IF NOT SHOW COMPLIANCE |
| | WITH 2004 FBC/M 507. |
| | |
| | 4) SHOW SUPPLY AND EXHAUST DUCTS WITH DUCT SIZES AND |
| | TYPE OF MATERIALS, FROM THE HOOD TO THE FANS ON THE |
| | ROOF, SEE FBC/M 506.3.4. |
| | |
| | 5) SHOW ON PLAN DISTANCE FROM ROOF TO EXHAUST FAN |
| | OUTLET, SEE 506.3.12.1. |
| | |
| | 6) SHOW ON PLAN DISTANCE BETWEEN EXHAUST FAN OUTLET TO |
| | SUPPLY FAN INLET, SEE NFPA 96(7.8.2). |
| | |
| | 7) PLEASE ADD A DETAIL TO THE PLAN SHOWING HOW THE |
| | SUPPLY AND EXHAUST FANS ARE TO BE SECURED TO THE ROOF |
| | TO WITHSTAND 140 MPH WINDS IN COMPLIANCE WITH 2004 FBC |
| | 1609. |
| | |