Plan Review Notes
Plan Review Notes For Permit 07050657
Permit Number 07050657
Review Stop M
Sequence Number 2
Notes
Date Text
2007-11-09 14:35:14PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) BE ADVISED MOST SHEETS IN ONE SET OF PLANS HAVE NOT
 BEEN SIGNED AND SEALED BUT ARE COPIES THESE ARE NOT
 ACCEPTABLE, SEE FAC 61G15-23.002. PLEASE CORRECT.
  
 2) PLANS PAGE A-1 SHOWS THE HOOD EXHAUST DUCT AS
 24"X24" IF THE EXHAUST FAN IS 3000 CFM'S THAT WOULD PUT
 THE AIR VELOCITY AT 750 FPM. PER 2004 FBC/M 506.3.4 AIR
 VELOCITY.
 GREASE DUCT SYSTEMS SERVING A TYPE I HOOD SHALL BE
 DESIGNED AND INSTALLED SO AS TO PROVIDE AN AIR VELOCITY
 WITHIN THE DUCT SYSTEM OF NOT LESS THAN 1,500 FEET PER
 MINUTE AND NOT GREATER THAN 2,500 FEET PER MINUTE.
 PLEASE CORRECT.
  
 3) IF THE HOOD IS U.L. APPROVED THEN PUT THE U.L.
 APPROVAL NUMBER ON THE PLAN. IF NOT SHOW COMPLIANCE
 WITH 2004 FBC/M 507.
  
 4) SHOW SUPPLY AND EXHAUST DUCTS WITH DUCT SIZES AND
 TYPE OF MATERIALS, FROM THE HOOD TO THE FANS ON THE
 ROOF, SEE FBC/M 506.3.4.
  
 5) SHOW ON PLAN DISTANCE FROM ROOF TO EXHAUST FAN
 OUTLET, SEE 506.3.12.1.
  
 6) SHOW ON PLAN DISTANCE BETWEEN EXHAUST FAN OUTLET TO
 SUPPLY FAN INLET, SEE NFPA 96(7.8.2).
  
 7) PLEASE ADD A DETAIL TO THE PLAN SHOWING HOW THE
 SUPPLY AND EXHAUST FANS ARE TO BE SECURED TO THE ROOF
 TO WITHSTAND 140 MPH WINDS IN COMPLIANCE WITH 2004 FBC
 1609.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]