Plan Review Notes
Plan Review Notes For Permit 07050657
Permit Number 07050657
Review Stop E
Sequence Number 2
Notes
Date Text
2007-11-13 08:28:16 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 ALL COMMENTS RELATE TO SHEETS E-1 AND E-2, UNLESS
 OTHERWISE NOTED. ALL CODE ARTICLES REFERENCED ARE 2005
 NEC UNLESS OTHERWISE NOTED.
 THESE ARE NEW COMMENTS THIS REVIEW BROUGHT FROM THE
 PANEL SCHEDULE SUBMITTED.
  
 1} CIRCUIT #11 IS MARKED AS APPLIANCE ON THE SCHEDULE,
 BUT SHOWN ON E-1 AS OUTLET FOR HOOD. CORRELLATE SAME.
  
 2} AIR HANDLER CIRCUIT 2,4 ON THE SCHEDULE, NOT LOCATED
 ON SHEET E-1.
  
 3} THE DOUGH MIXER CIRCUIT 8,10 ON THE SCHEDULE, NOT
 LOCATED ON E-1.
  
 4} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND 471
 FS, RESPECTIVELY.
  
 PLEASE REMOVE OLD SHEETS, INSERT NEW ONES, SUBMIT OLD
 SHEETS TO EXPEDITE REVIEW AND SUBMIT WRITTEN RESPONSE
 TO THE COMMENTS MADE IN THIS REVIEW.
  
 FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN THE
 FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE INDICATE
 THE CODE CYCLES UNDER WHICH THIS PLAN WAS DESIGNED.
  
  
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]