Plan Review Notes
Plan Review Notes For Permit 07050657
Permit Number 07050657
Review Stop B
Sequence Number 2
Notes
Date Text
2007-11-20 11:48:26 
  
 BUILDING PLAN REVIEW
 PERMIT: 07050657
 ADD: 1700 45TH STREET #1738
 CONT: RENOUVELLE INC
 TEL: (561)841-0502
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 2ND
 ACTION: DENIED
  
 NOTE:DUE TO THE FACT THAT TWO NEW SETS OF PLANS ARE
 SUBMITTED, AND ONE SET OF THE OLD SET WAS NOT
 RE-SUBMITTED, NEW COMMENTS MAY BE INCLUDED WITH THIS
 REVIEW.
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1C) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 REVISIONS.
  
  
 2)2004 FBC EXISTING
 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
  
 3)THE CODE REFERENCE TO ?SAFEGUARDS DURING
 CONSTRUCTION? IS INCORRECT. CHAPTER 13 IN THE 2004 FBC
 IS THE ENERGY EFFICIENCY CHAPTER. SEE FBC CHAPTER 33
 FOR INFORMATION REGARDING ?SAFEGUARD DURING
 CONSTRUCTION?.
  
 4)INDICATE ON THE FLOOR PLAN HOW THE CASH REGISTER
 WILL MEET THE REQUIREMENTS OF SECTION 11-7. SHOW THE
 ELEVATION DETAIL OF THE FRONT COUNTER WHERE THE
 CUSTOMERS WILL INTERACT WITH THE CASHIER.
  
 5)SUBMIT AN EXISTING AND A PROPOSED FLOOR PLAN
 SHOWING ALL DEMOED SYSTEMS AND ALL NEW SYSTEMS
 INCLUDING PLUMBING, ELECTRIC, MECHANICAL AND WALLS.
 THESE DRAWINGS WILL CLARIFY THE AREAS WHERE THE
 PROPOSED WORK WILL TAKE PLACE. THE BUILDING OFFICIAL
 MAY REQUIRE DETAILS AND OTHER NECESSARY DATA TO
 DESCRIBE THE PROJECT. WILL THE NEW 6? WALL ATTACHED TO
 THE DECK ABOVE OR THE CEILING GRID?WHEN THE WALL IS
 CONSTRUCTED THE SPRINKLER SYSTEM WILL HAVE NO EFFECT ON
 THE CORRIDOR CREATED. SHOW ON THE DRAWINGS HOW THIS
 PROBLEM WILL BE RECTIFIED.
  
 6)THE FLAME SPREAD AND SMOKE-DEVELOPED INDEX IN
 ACCORDANCE WITH FBC803 AND TABLE 803.5
  
 7)THE OCCUPANT LOAD OF THE AREA SHALL BE SHOWN ON THE
 DRAWINGS. SEE TABLE 1004.1.2 WHEN DESIGNING THE
 OCCUPANT LOAD.
  
 8)TWO COMPLETE SETS OF CONSTRUCTION DOCUMENTS SHALL
 BE PREPARED BY THE DESIGN PROFESSIONAL FOR REVIEW. ONE
 SET OF THE DRAWINGS IS A PHOTO-COPY SET. THE RAISED
 SEAL OF THE ENGINEER IS MISSING FROM THE DRAWINGS.
 SUBMIT TWO SETS OF DRAWINGS WITH THE ORIGINAL SEAL,
 SIGNATURE AND DATE OF THE ENGINEER OF RECORD. FBC
 106.1.
  
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  
  
  