| 2007-06-09 08:22:55 | DENIED; | | | 1.PLANS ARE REQUIRED TO BE APPROVED BY THE DEPARTMENT | | | OF BUSINESS AND PROFESSIONAL REGULATION DIVISION OF | | | HOTEL AND RESTAURANTS. INFORMATION REQUIRED CAN BE | | | FOUND AT | | | TTP://WWW.MYFLORIDA.COM/DBPR/HR/FORMS/INDEX.SHTML. | | | PLANS MUST BE STAMP AND REPORT ATTACHED TO PLANS FROM | | | DPR BEFORE RESUB TO BUILDING DEPARTMENT. | | | 2. ALL GREASE TRAP INSTALLATIONS MUST BE APPROVED BY | | | WPB UTILITIES DEPARTMENT. PLEASE CONTACT RODNEY COMPO | | | 822-2272 OR CALVN WILLIAMS 822-2284. | | | 3. THE 2 COMPARTMENT SINK SHOULD BE A 3 COMPARTMENT, | | | HEALTH DEPARTMENT REQUIREMENT. THE SINK SHALL BEAN | | | INDURECT WASTE SEE FBC-2004 PLUMBING SECTION 802.1. | | | 4. 20% OF COST OF JOB SHALL BE USED TO MAKE THE SHOP | | | ACCESSIBLE. PLEASE SHOW WHAT WORK WILL BE DONE AND | | | ESTIMATEDCOST ON PLANS. | | | 5. CAN WASH SHALL DRAIN TO GREASE WASTE. DRAIN FIELD | | | NOT PERMITED. SECTION 701.2. | | | 6. PLUMBING NOTES #6 CHANGE THE SECTION, (NO MORE THAN | | | 15' FROM VENTEDSEWER) TO "SHALL COMPLY WITH FBC-2004 | | | PLUMBING TABLE 906.1. | | | 7. A REDUCED PRESSURE BACKFLOW PREVENTER IS REQUIRED ON | | | WATER SERVICE. IF ONE EXISTS STATE ON PLANS IF NOT SHOW | | | ON WATER RISER. | | | 8. SIZE ALL DRAINAGE PIPE ON RISER DIAGRAM. | | | PLUMBING PLAN REV BY; | | | JOHN LEECH | | | 805-6695 |
|