| Plan Review Notes For Permit 07050657 |
| Permit Number |
07050657 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-06-11 08:44:48 | *** DENIED *** | | | 1) PLEASE SUBMIT ENGINEERING FOR KITCHEN EXHAUST HOOD | | | WITH ALL PERTINENT INFORMATION SPECIFIC TO THIS JOB, | | | SPECIFICATION SHEETS ARE TO GENERIC. | | | | | | 2) SHOW ANCHORING DETAIL FOR FANS AND HANGING DETAIL | | | FOR HOOD. | | | | | | 3) SHOW LOCATION OF EXHAUST FAN AND SUPPLY FAN. | | | | | | 4) BE ADVISED ADDITIONAL PERMITS WILL BE REQUIRED FOR | | | KITCHEN HOOD AND FIRE SUPPRESSION. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|