Plan Review Notes For Permit 07050657
Permit Number 07050657
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-06-12 10:41:09******DENIED*****
  
  
 1.THE SUBMITTED PLANS DO NOT INDICATE WHAT THE
 MODIFICATIONS TO THE EXISTING STRUCTURE ARE TO BE
 CONDUCTED.IS THIS A CHANGE OF OCCUPANCY?DOES THE
 OCCUPANCY HAVE FIRE SPRINKLER AND/OR FIRE ALARM
 DEVICES?
  
 2.THE 2003 EDITION OF NFPA 101 AND THE 2004 EDITION
 OF THE FLORIDA FIRE PREVENTION CODE SHALL BE
 REFERENCED.
  
 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 4.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE THE SITE AT THE END OF EACH SHIFT
 OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 5.THE REMOVAL AND/OR REPLACEMENT OF BUILDING
 MATERIALS & SUPPLIES SHALL NOT INTERFERE OR HINDER
 EMERGENCY RESPONSE ACCESS TO THE PROPERTY OR VICINITY
 THEREOF (INCLUDING FIRE LANES).
  
 6.IF THE BUILDING OR PORTION OF THE BUILDING IS TO BE
 OCCUPIED DURING THE SCOPE OF WORK, REQUIRED MEANS OF
 EGRESS AND REQUIRED FIRE PROTECTION FEATURES SHALL BE
 OPERATIONAL AND MAINTAINED.
  
 7.BASED UPON THE OCCUPANCY TYPE, INDICATE THE
 INTERIOR WALL AND CEILING MATERIALS IN EXITS, EXIT
 ACCESS CORRIDORS, AND IN ALL OTHER AREAS.BE SPECIFIC
 AS TO CLASS A, CLASS B, OR CLASS C.
  
 8.PROVIDE LOCATION OF THE 2A:10BC RATED FIRE
 EXTINGUISHER(S) SATISFYING THE 75' TRAVEL DISTANCE.
  
 9.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE
 HOOD'S SUPPRESSION SYSTEM
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHEAL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722