Plan Review Notes
Plan Review Notes For Permit 07050657
Permit Number 07050657
Review Stop E
Sequence Number 1
Notes
Date Text
2007-06-01 13:49:40 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} STANDARD 120 AMP OUTLETS ARE INDICATED ON A 30 AMP
 BREAKER, CIRCUIT #11. ALSO THE 14 AMP HOOD IS SHOWN ON
 THAT CIRCUIT. 210.23(B).
  
 2} PLEASE INDICATE THE CIRCUIT NUMBERS AT THE DEVICES.
 106.3.5.1 FBC AS AMENDED.
  
 3} INDICATE THE CIRCUIT NUMBERS FOR THE LIGHTS SO THAT
 COMPLIANCE WITH 700.12(F)(4) FOR THE EMERGENCY
 FIXTURES, CAN BE REVIEWED.
  
 AN ELECTRICAL PERMIT IS REQUIRED PER 105.1 FBC AS
 AMENDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  