| Plan Review Notes For Permit 07050652 |
| Permit Number |
07050652 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-06-12 15:54:11 | ***DENIED*** | | | | | | 1) PLANS PREVIOUSLY SUBMITTED UNDER EXPIRED PERMIT WERE | | | APPROVED AND STAMPED. IT APPEARS THAT THE PLANS WERE | | | CODE COMPLIANT. PLEASE SUBMIT (2) NEW SETS OF PLANS FOR | | | REVIEW. THE SET THAT HAS ALREADY BEEN STAMPED MAY BE | | | SUBMITTED AND MARKED (OLD) TO BE USED FOR REFERENCE FOR | | | PLAN REVIEW. | | | | | | 2) IF THIS BUILDING IS PROTECTED BY AN AUTOMATIC FIRE | | | SPRINKLER SYSTEM, THE FIRE ALARM SHALL BE UL CERTIFIED | | | FOR CENTRAL STATION SERVICE. THE SEQUENCE OF OPERATION | | | ILLUSTRATES FLOW SWITCH DEVICES, BUT THIS IS NOT SHOWN | | | ON RISER OR DRAWINGS. PLEASE ADVISE AND INDICATE ON | | | DRAWINGS AT TIME OF RE-SUBMITTAL. | | | | | | 3) SINCE THIS BUILDING CAN BE CLASSIFIED AS A HIGHRISE, | | | THE FIRE ALARM SYSTEM SHALL MEET THE REQUIREMENTS FOR | | | SURVIVABILITY IN ACCORDANCE WITH NFPA 72. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|