| 2007-10-26 11:10:20 | RESIDENTIAL ADDITION BUILDING REVIEW THIRD CHECKLIST. |
| | REVIEW UNDER FLORIDA RESIDENTIAL CODE 2004, EXISTING |
| | BUILDING CODE 2004 AND FBC 2004 WITH 2006 REVISIONS. |
| | |
| | 1- REVISE PLYWOOD SHEATHING NAILING SPACING AS REQUIRED |
| | BY SEC. R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL CODE. |
| | NEED TO PROVIDE MIN. 8D RING SHANK NAILS AT 4" O.C.IN |
| | ROOF ZONE 3. REVISEPLY WOOD SHEATHING FASTENER |
| | SCHEDULE, WALL SECTION A/A-2 AND WALL SECTION B/A-2 AS |
| | REQUIRED. (REPEAT COMMENT). |
| | |
| | 2- THIS IS THE FIRST TIME THE ENERGY CALCULATIONS ARE |
| | SUBMITTED. |
| | A) ENERGY CALCULATIONS ARE INCOMPLETE.INFORMATION |
| | FOR TABLE 6C-1AND 6C-2 WAS NOT SUBMITTED. NEED TO |
| | PROVIDE THIS INFORMATION. SEC. 13-600.1.C.1 FBC 2004. |
| | |
| | B) COMPLETE ALL INFORMATION ON TOP OF FORM. |
| | |
| | 3-FRENCH DOORS NOA 02-1211.10 SUBMITTED DOESN'TMEET |
| | THE DESIGN PRESSURES CALCULATED BY THE ENGINEER (+75.0 |
| | AND -75.0).NEED TO PROVIDE PRODUCT APPROVAL THAT |
| | MEETS OR EXCEEDS THE CALCULATED DESIGN PRESSURES. |
| | |
| | 4- SINGLE HUNG WINDOWNOA 02-0507.06 DOESN'T MEET THE |
| | DESIGN PRESSURES CALCULATED BY THE ENGINEER (+75.0AND |
| | -80.0). NEED TO PROVIDE PRODUCT APPROVAL THAT MEETS OR |
| | EXCEEDS THE CALCULATED DESIGN PRESSURES. |
| | |
| | 5- ON PREVIOUS SUBMITTALS CONTRACTOR SUBMITTED PRODUCT |
| | APPROVALS FOR DOORS AND WINDOWS WITH MISSILE IMPACT |
| | GLASS. NOW PRODUCT APPROVALS SUBMITTED DON'T HAVE THE |
| | MISSILE IMPACT GLASS. NEED TO PROVIDE PRODUCT APPROVALS |
| | WITH IMPACT GLASS OR PROVIDEPRODUCT APPROVAL FOR |
| | STORM SHUTTERS AND CLEARLY INDICATE ANCHOR TYPE AND |
| | SPACING ON THE SHUTTER DRAWINGS TO VERIFY COMPLIANCE |
| | WITH PROPOSED INSTALLATION. SEC. 106.1.2 CITY |
| | AMENDMENTS TO FBC 2004 IN REGARDS TO WIND LOADS SEC. |
| | 1609 FBC 2004. |
| | |
| | 6- ENGINEER TO SPECIFY ROOF TILE FASTENING AS REQUIRED |
| | BY SEC. 106.1.1.2 CITY AMENDMENTS TO FBC 2004. |
| | INFORMATION SUBMITTED ONLY SPECIFIES TO USE 10D X 3" |
| | NAILS.NEED TO SPECIFY HOW MANY NAILS ARE REQUIRED TO |
| | RESIST THE ENGINEER'S UPLIFT MOMENT CALCULATIONS. |
| | PRODUCT APPROVAL IS ONLY TO VERIFY THAT PROPOSED |
| | INSTALLATION MEETS THE DESIGN CRITERIA. |
| | ***NOTE: IF USING POLYFOAM, THEN PROVIDE PRODUCT |
| | APPROVAL FOR LISTED POLYFOAM SPECIFIED ON THE CONCRETE |
| | TILE NOA SUBMITTED. |
| | |
| | 7- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| | PRODUCT APPROVALS ARE NOT REVIEWED BY THE ENGINEER OF |
| | RECORD AND IT DOESN'TPROVIDE THE NAME OF THE ENGINEER |
| | WHO REVIEWED THE PRODUCT APPROVALS. (REPEAT COMMENT). |
| | |
| | 8- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH |
| | COUNTY TO VERIFY IF IMPACT FEES ARE DUE. BRING BACK |
| | STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. |
| | (REPEAT COMMENT). |
| | |
| | 9- NEED RE-RECORDED NOTICE OF COMMENCEMENT AS REQUIRED |
| | BY SEC. 713.13 FLORIDA STATUTE. |
| | |