| 2007-08-20 17:00:42 | RESIDENTIAL ADDITION BUILDING REVIEW SECOND CHECKLIST. |
| | |
| | REVIEW DONE UNDER 2004 FLORIDA RESIDENTIAL CODE AND |
| | 2004FBC WITH 2006 REVISIONS. |
| | |
| | 1- SHEET A1: |
| | A) ROOF DEAD LOAD IS INCORRECT.IT CAN'T BE 10PSF |
| | IF INSTALLING CONCRETE TILE. REVISE AS REQUIRED. |
| | PROVIDE ACTUAL DEAD LOAD. SEC. 106.1.2 CITY AMENDMENTS |
| | TO FBC 2004. |
| | |
| | B) WRONG CONSTRUCTION TYPE.SEE SEC. 602.1 FBC 2004 |
| | FOR CORRECT TYPE OF CONSTRUCTION. |
| | ***NOTE: KEEP IN MIND CONSTRUCTION OF ARCHED OPENING TO |
| | DETERMINE CORRECT TYPE OF CONSTRUCTION. |
| | |
| | 2- SHEET A2: |
| | A) REVISE PLYWOOD SHEATHING NAILING SPACING FOR ROOF |
| | ZONE #3. SEE SEC. R803.2.3.1 OF 2004 FLORIDA |
| | RESIDENTIAL CODE AND REVISE AS REQUIRED. |
| | ***NOTE: REVISE PLYWOOD SHEATHING FASTNER SCHEDULE AND |
| | INFORMATION IN ALL WALL SECTIONS. |
| | |
| | B) PROVIDE CORRECT INFORMATION FOR SIZE OF |
| | CONTINUOUS VENT AT ATTIC AREA.IT CAN'T BE 7'X12" AT |
| | 24"O.C. IF IT'S A CONTINUOUS VENTILATION STRIP. REVISE |
| | INFORMATION AS REQUIRED ON BOTH WALL SECTIONS. SEC. |
| | R806 OF 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | C) REVISE REINFORCEMENT BARS SPECIFIED FOR RAKED |
| | BEAM AT RAKED GABLE END SECTION. SPECIFICATIONS NEED TO |
| | MATCH CONCRETE BEAM SCHEDULE. |
| | |
| | 3- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH |
| | COUNTY(2300 N. JOG RD (561)233-5115)TO VERIFY IF |
| | IMPACT FEES ARE DUE OR NOT. BRING BACK STAMPED PLANS |
| | AND COPY OF PAID RECEIPT IF FEES ARE DUE. REPEAT |
| | COMMENT FROM PREVIOUS CHECKLIST. |
| | |
| | 4- NEED RE-RECORDED NOTICE OF COMMENCEMENT AS REQUIRED |
| | BY SEC. 713.13 FLORIDA STATUTE. REPEAT COMMENT FROM |
| | PREVIOUS CHECKLIST. |
| | |
| | 5- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| | 13-600 FBC 2004. REPEAT COMMENT FROM PREVIOUS |
| | CHECKLIST. |
| | ***NOTE: MAKE SURE CORRECT 2006 REVISED FORM IS USED. |
| | |
| | 6- PROVIDE CALCULATIONS FOR CALCULATED DESIGN PRESSURES |
| | AT WINDOWS AND DOORS OPENINGS.SEC. 106.1.2 CITY |
| | AMENDMENTS TO FBC 2004.PRESSURES ARE TOO LOW COMPARED |
| | TO TABLE 1609..6.2.1(2) FBC 2004 AND ASCE 7-02. REPEAT |
| | COMMENT FROM PREVIOUS CHECKLIST. |
| | |
| | 7- SPECIFY ROOF TILE FASTENING AS REQUIRED BY SEC. |
| | 106.1.1.2 CITY AMENDMENTS TO FBC 2004.REPEAT COMMENT |
| | FROM PREVIOUS CHECKLIST. |
| | |
| | 8- PROVIDE 2 COPIES OF PRODUCT APPROVALSAS REQUIRED |
| | BY DCA RULE 9B-72 FOR: |
| | A) ARCHED FIXED WINDOW. PRODUCT APPROVAL SUBMITTED |
| | IS FOR RECTANGULAR WINDOWS. NEED ARCHED WINDOWS PRODUCT |
| | APPROVAL. |
| | |
| | B) ALL SIMPSON CONNECTORS SPECIFIED ON PLANS. NEED |
| | TWO COPIES AND NEED FLORIDA PRODUCT APPROVAL COVER PAGE |
| | FOR A35 CONNECTOR. GO TO WWW.FLORIDABUILDING.ORG TO |
| | DOWNLOAD CORRECT PRODUCT APPROVAL COVER PAGE. |
| | ***NOTE: PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL |
| | COVER PAGE AND SHEET WHERE CONNECTOR IS TO SAVE ON |
| | PAPERWORK. |
| | |
| | 9- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3CITY AMENDMENTS TO FBC 2004. |
| | REPEAT COMMNET FROM PREVIOUS CHECKLIST. |
| | ***NOTE: MAKE SURE ENGINEER'S NAME IS SHOWN ON THE |
| | PRODUCT APRPOVAL REVIEW STAMP. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |