2007-08-20 17:00:42RESIDENTIAL ADDITION BUILDING REVIEW SECOND CHECKLIST.
  
 REVIEW DONE UNDER 2004 FLORIDA RESIDENTIAL CODE AND
 2004FBC WITH 2006 REVISIONS.
  
 1- SHEET A1:
 A) ROOF DEAD LOAD IS INCORRECT.IT CAN'T BE 10PSF
 IF INSTALLING CONCRETE TILE. REVISE AS REQUIRED.
 PROVIDE ACTUAL DEAD LOAD. SEC. 106.1.2 CITY AMENDMENTS
 TO FBC 2004.
  
 B) WRONG CONSTRUCTION TYPE.SEE SEC. 602.1 FBC 2004
 FOR CORRECT TYPE OF CONSTRUCTION.
 ***NOTE: KEEP IN MIND CONSTRUCTION OF ARCHED OPENING TO
 DETERMINE CORRECT TYPE OF CONSTRUCTION.
  
 2- SHEET A2:
 A) REVISE PLYWOOD SHEATHING NAILING SPACING FOR ROOF
 ZONE #3. SEE SEC. R803.2.3.1 OF 2004 FLORIDA
 RESIDENTIAL CODE AND REVISE AS REQUIRED.
 ***NOTE: REVISE PLYWOOD SHEATHING FASTNER SCHEDULE AND
 INFORMATION IN ALL WALL SECTIONS.
  
 B) PROVIDE CORRECT INFORMATION FOR SIZE OF
 CONTINUOUS VENT AT ATTIC AREA.IT CAN'T BE 7'X12" AT
 24"O.C. IF IT'S A CONTINUOUS VENTILATION STRIP. REVISE
 INFORMATION AS REQUIRED ON BOTH WALL SECTIONS. SEC.
 R806 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 C) REVISE REINFORCEMENT BARS SPECIFIED FOR RAKED
 BEAM AT RAKED GABLE END SECTION. SPECIFICATIONS NEED TO
 MATCH CONCRETE BEAM SCHEDULE.
  
 3- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY(2300 N. JOG RD (561)233-5115)TO VERIFY IF
 IMPACT FEES ARE DUE OR NOT. BRING BACK STAMPED PLANS
 AND COPY OF PAID RECEIPT IF FEES ARE DUE. REPEAT
 COMMENT FROM PREVIOUS CHECKLIST.
  
 4- NEED RE-RECORDED NOTICE OF COMMENCEMENT AS REQUIRED
 BY SEC. 713.13 FLORIDA STATUTE. REPEAT COMMENT FROM
 PREVIOUS CHECKLIST.
  
 5- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 13-600 FBC 2004. REPEAT COMMENT FROM PREVIOUS
 CHECKLIST.
 ***NOTE: MAKE SURE CORRECT 2006 REVISED FORM IS USED.
  
 6- PROVIDE CALCULATIONS FOR CALCULATED DESIGN PRESSURES
 AT WINDOWS AND DOORS OPENINGS.SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.PRESSURES ARE TOO LOW COMPARED
 TO TABLE 1609..6.2.1(2) FBC 2004 AND ASCE 7-02. REPEAT
 COMMENT FROM PREVIOUS CHECKLIST.
  
 7- SPECIFY ROOF TILE FASTENING AS REQUIRED BY SEC.
 106.1.1.2 CITY AMENDMENTS TO FBC 2004.REPEAT COMMENT
 FROM PREVIOUS CHECKLIST.
  
 8- PROVIDE 2 COPIES OF PRODUCT APPROVALSAS REQUIRED
 BY DCA RULE 9B-72 FOR:
 A) ARCHED FIXED WINDOW. PRODUCT APPROVAL SUBMITTED
 IS FOR RECTANGULAR WINDOWS. NEED ARCHED WINDOWS PRODUCT
 APPROVAL.
  
 B) ALL SIMPSON CONNECTORS SPECIFIED ON PLANS. NEED
 TWO COPIES AND NEED FLORIDA PRODUCT APPROVAL COVER PAGE
 FOR A35 CONNECTOR. GO TO WWW.FLORIDABUILDING.ORG TO
 DOWNLOAD CORRECT PRODUCT APPROVAL COVER PAGE.
 ***NOTE: PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL
 COVER PAGE AND SHEET WHERE CONNECTOR IS TO SAVE ON
 PAPERWORK.
  
 9- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3CITY AMENDMENTS TO FBC 2004.
 REPEAT COMMNET FROM PREVIOUS CHECKLIST.
 ***NOTE: MAKE SURE ENGINEER'S NAME IS SHOWN ON THE
 PRODUCT APRPOVAL REVIEW STAMP.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712