Plan Review Notes
Plan Review Notes For Permit 07050647
Permit Number 07050647
Review Stop B
Sequence Number 1
Notes
Date Text
2007-06-27 18:58:25BUILDING REVIEW CHECKLIST:
 1-SHEET A1:
 A) UPDATE WIND INFORMATION. CURRENT CODE IS 2004
 FLORIDA RESIDENTIAL CODE, 2004 FBCWITH CORRESPONDING
 2006 REVISIONS AND ASCE 7-02.. REVISE ALL NOTES AS
 REQUIRED.
  
 B) WHY PROVIDING BALCONY NOTES IF THERE IS NOT
 BALCONY IN THIS PROJECT.
  
 C) SPECIFY ALL LIVE AND DEAD LOADS, INCLUDING THE
 ATTIC LIVE LOADS. SEE SEC. R301 AND TABLE R301.5 OF
 2004 FLORIDA RESIDENTIAL CODE FOR ALL LOADS TO BE
 CONSIDERED IN THE DESIGN OF THE STRUCTURE.
  
 D) SPECIFY CONSTRUCTION TYPE AS REQUIRED BY SEC.
 602.1 FBC 2004.
  
 E) REVISE TABLES REFERENCED IN THE WIND INFORMATION
 SECTION. SEE REVISED FBC 2004 TABLES AND REVISE ALL
 INFORMATION AS REQUIRED.
  
 2- SHEET A2:
 A) SPECIFY ATTIC ACCESS SIZE.SEC. R807 OF 2004
 FLORIDA RESIDENTIAL CODE. HANDWRITTEN INFORMATION IS
 NOT ALLOWED.
  
 B) INFORMATION ON CONCRETE BEAM SCHEDULE DOESN'T
 MATCH INFORMATION SHOWN ON TYPICAL WALL SECTION AND
 WALL SECTION A/A-2.
 *** ALSO, REVISE NUMBERING FOR WALL SECTIONS. BOTH
 CAN'T BE A/A-2.
  
 C) REVISE PLYWOOD SHEATHING FASTENER SCHEDULE. SEE
 SEC. R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL CODE FOR
 MIN. NAIL TYPE AND SPACING TO BE USED. ALSO, SEE MIN.
 FASTENER SPACING FOR ROOF ZONE 3 AND REVISE AS
 REQUIRED.
 *** NOTE: INFORMATION ON ROOF SHEATHING FASTENER
 SCHEDULE TO MATCH INFORMATION ON WALL SECTIONS.
  
 D) UPDATE ANCHOR SCHEDULE. SEE CURRENT CATALOG AND
 REVISE AS REQUIRED. OTHERWISE, PROVIDE COMPLETE
 ENGINEERING ANALYSIS FOR FASTENER TYPE AND NUMBER THAT
 DIFFERS FROM THAT TESTED AND PUBLISHED BY THE
 MANUFACTURER. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
  
 E) SPECIFY SIZE OF CONTINUOUS ATTIC VENT. SEC. R806
 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 F) FOOTING FOR EXISTING PRIVACY WALL CAN'T BE AS
 SHOWN ON PLANS BECAUSE WALL IS LOCATED ON ZERO LOT LINE
 AND IT CAN'TENCROACH ON NEIGHBOR'S PROPERTY. VERIFY
 IN FIELD TYPE OF EXISTING FOOTING AND DIMENSIONS.
 ENGINEER NEEDS THIS INFORMATION TO SHOW THAT PROPOSED
 LOAD WILL BE RESISTED BY EXISTING FOOTING.SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 G) PROVIDE COMPLETE SPECS FOR ATTACHMENT OF VERTICAL
 REINFORCEMENT TO EXISTING PRIVACY WALL.INFORMATION
 GIVEN DOESN'T PROVIDE ANY INFORMATION OTHER THAN DOWEL
 TO EXISTING BEAM. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
  
 H) WALL SECTION AT PRIVACY WALL TO SHOW PROPOSED TE1
 FOOTING AS SHOWN ON FOUNDATION PLAN. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 I) INFORMATION GIVEN ON RAKED GABLE END DETAIL
 DOESN'T MATCH INFORMATION GIVEN ON CONCRETE BEAM
 SCHEDULE.
  
 J) FOUNDATION PLAN AND COLUMN SCHEDULE TO BE
 COORDINATED. SPECIFY ON FOUNDATION PLAN COLUMN TYPE.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 3- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY(2300 N. JOG RD (5610233-5115)TO VERIFY IF
 IMPACT FEES ARE DUE.BRING BACK STAMPED PLANS AND COPY
 OF PAID RECEIPT IF FEES ARE DUE.
  
 4- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
  
 5- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 13-600 OF FBC 2004.
 ***NOTE; MAKE SURE 2006 REVISED FORM IS USED.
  
 6- PROVIDE COMPLETE FRAMING DETAIL AT WINDOW ARCHED
 OPENING. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 7- OPENING DESIGN PRESSURES ARE TOO LOW BASED ON
 OPENING LOCATION/ SIZE AND REVISED TABLE 1609.6.2.1(2)
 OF FBC 2004. PROVIDE CALCULATIONS FOR THE DESIGN
 PRESSURES SHOWN ON DRAWINGS. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 8- SPECIFY ROOF TILE FASTENING AS REQUIRED BY SEC.
 106.1.1.2 CITY AMENDMENTS TO FBC 2004.ENGINEER OF
 RECORD SPECIFIES FASTENING. PRODUCT APPROVAL IS JUST TO
 VERIFY THAT THE TILE WILL MEET THE DESIGNER CRITERIA.
  
 9- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) FIXED WINDOW. NOA 02-0123.03 SUBMITTED IS FOR
 SMALL MISSILE IMPACT.NEED TO PROVIDE PRODUCT APPROVAL
 FOR LARGE MISSILE IMPACT FOR OPENINGS BELOW 30'-0".
  
 B) ROOF TILE.
  
 C) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS. PROVIDE JUST THE FLORIDA PRODUCT APPROVAL COVER
 PAGE AND PAGE SHOWING THE CONNECTOR ONLY.
  
 10- ENGINEER OF RECORD TO REVIEW IN WRITING (NOT
 SIGNING AND SEALING) ALL PRODUCT APPROVALS AS REQUIRED
 BY SEC. 106.3.3CITY AMENDMENTS TO FBC 2004.
  
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712