Plan Review Notes
Plan Review Notes For Permit 07050635
Permit Number 07050635
Review Stop E
Sequence Number 1
Notes
Date Text
2007-05-29 10:32:00 
  
 DENIED/INCOMPLETE INFORMATION
  
 THERE IS AN ELECTRICAL "PANEL" SHOWN ON THE ELECTRICAL
 SCHEMATIC. THIS WOULD APPEAR TO BE A "POOL PANEL". IF
 IT IS EXISTING PLEASE INDICATE ON THE PLAN. IF IT IS
 BEING INSTALLED AS PART OF THIS PERMIT, SUBMIT THE
 FOLLOWING DETAILS ON THE PLAN: FEEDER SIZE AND OCP,
 GROUND PER 250.122 OR 250.66 IF ON A SEPARATE
 STRUCTURE.
  
 INDICATE COMPLIANCE WITH ARTICLE 680.26 FOR
 EQUIPOTENTIAL BONDING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718