| Notes |
| Date |
Text |
| 2007-05-29 10:32:00 | | | | | | | DENIED/INCOMPLETE INFORMATION | | | | | | THERE IS AN ELECTRICAL "PANEL" SHOWN ON THE ELECTRICAL | | | SCHEMATIC. THIS WOULD APPEAR TO BE A "POOL PANEL". IF | | | IT IS EXISTING PLEASE INDICATE ON THE PLAN. IF IT IS | | | BEING INSTALLED AS PART OF THIS PERMIT, SUBMIT THE | | | FOLLOWING DETAILS ON THE PLAN: FEEDER SIZE AND OCP, | | | GROUND PER 250.122 OR 250.66 IF ON A SEPARATE | | | STRUCTURE. | | | | | | INDICATE COMPLIANCE WITH ARTICLE 680.26 FOR | | | EQUIPOTENTIAL BONDING. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|