| Date |
Text |
| 2007-11-03 17:13:22 | DENIED |
| | REFERENCE: FBC-2004 FUEL GAS |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | 1. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING |
| | INFORMATION IS REQUIRED FOR THE GAS PERMIT: |
| | |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | ****RESPONSE NOTED, BUT COMMENT NOT COMPLETLY |
| | ADDRESSED. LENGTHS OF PIPE NOT SHOWN. |
| | |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE IF BEING USED. ****RESPONSE |
| | NOTED, BUT COMMENT NOT ADDRESSED. PIPE TYPE NOT |
| | INDICATED ON LEGEND. |
| | |
| | C. OK |
| | |
| | D. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | ****RESPONSE NOTED, BUT THIS WILL BE VERIFIED WHEN ALL |
| | CUT SECTION LENGTHS ARE INDICATED ON THE GAS ISOMETRIC |
| | RISER DIAGRAM. |
| | |
| | E. OK |
| | |
| | F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. THE |
| | MANUF. SPECIFICATION SHEETS FOR ALL GAS APPLIANCES |
| | INCLUDING THE RTU ARE REQUIRED AND SHALL SHOW A LISTING |
| | AS WELL AS THE BTU LOAD OF THE APPLIANCE. |
| | |
| | G. N/A |
| | H. N/A |
| | |
| | I. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. |
| | ****RESPONSE NOTED, BUT THE COMMENT IS NOT ADDRESSED. |
| | |
| | **********NEW COMMENTS*********** |
| | |
| | 1B. SEDIMENT TRAPS REQUIRED BY SECTION 408.4 SHALL BE |
| | SHOWN ON THE GAS RISER DIAGRAM. |
| | |
| | 2B. SHUT OFF VALVES SHALL BE PROVIDED FOR EACH GAS |
| | APPLIANCE. SECTION 409.5. PLEASE SHOW THE SHUT OFF |
| | VALVE FOR THE RTU UNIT. ALL SHUT OFF VALVES SHALL BE |
| | ACCESSIBLE PER SECTION 409.5. |
| | |
| | 3B. SEE ATTACHED SHEET CONCERNING THE DESIGN |
| | PROFESSIONAL AND FS 553.80(2)(B). THIS IS GIVEN AS A |
| | NOTICE ONLY AT THIS TIME. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | |