| 2007-10-24 13:33:11 | ***DENIED*** |
| | |
| | SOME OF THE PREVIOUS COMMENTS WERE ADDRESSED DIRECTLY |
| | ON THE PLANS. (SHT A-1) A RESPONSE LETTER (2ND REQUEST) |
| | WOULD BE HELPFUL AND AS STATED IN THE FIRST REVIEW WILL |
| | HELP EXPEDITE THE PLAN REVIEW PROCESS. |
| | |
| | 1) OK |
| | |
| | 2) OK |
| | |
| | 3) OK |
| | |
| | 4) COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL |
| | BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR |
| | MOVE FREQUENTLY AS NECESSARY FOR SAFE OPEARTION. |
| | |
| | 5) THE SCOPE OF WORK SHALL NOT INTERFERE OR HINDER |
| | EMERGENCY RESPONSE ACCESS TO THE PROPERTY OR VICINITY |
| | THEREOF (INCLUDING STREETS, ALLEYS, FIRE LANES ETC). |
| | |
| | 6) CLASSIFY THE HAZARD OF CONTENTS OF |
| | BUILDING/STRUCTURE AS LOW, ORDINARY OR HIGH. |
| | |
| | 7) OK |
| | |
| | 8) LOCKS ON EGRESS DOORS SHALL NOT REQUIRE THE USE OF A |
| | KEY, TOOL OR SPECIAL KNOWLEDGE OR EFFORT OF OPERATION |
| | FROM THE EGRESS SIDE. (NO DOOR SCHEDULE) |
| | |
| | 9) OK |
| | |
| | 10) AN EXIT SIGN LIGHT WITH BATTERY BACK-UP CAPABILITY |
| | SHALL BE REQUIRED TO DIRECT PERSON(S) FROM THE COOKING |
| | PREPARATION AREA. |
| | |
| | 11) SPECIFY THE INTERIOR WALLS AND CEILING FINISH |
| | MATERIALS IN TERMS OF CLASSA,B OR C. |
| | |
| | 12) COMMERCIAL COOKING EQUIPMENT TO COMPLY WITH NFPA |
| | 96, 2001 EDITION. |
| | |
| | 13) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR |
| | HOOD AND SUPPRESSION SYSTEMS. PLANS INDICATE SEPARATE |
| | PERMIT FOR FIRE SPRINKLER WHICH PLANS ALSO STATE NOT |
| | APPLICABLE. |
| | |
| | |
| | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL |
| | FIRE PLAN REVIEW |
| | FIRE PREVENTION (561) 804-4756 |