| 2007-10-20 10:28:11 | BUILDING PLAN REVIEW |
| | PERMIT: 07050622 |
| | ADD: 540 CLEMATIS |
| | CONT: KDN CONSTRUCTION |
| | TEL: (561)662-1002 |
| | |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2NDREVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | 2 ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT |
| | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 3)PLANS INDICATE THIS BUILDING TO BE A TYPE IIB |
| | UNPROTECTED, UNSPRINKLERED, THIS BUILDING IS |
| | APPROXIMATELY 3,150 SQ FT. PLEASE INDICATE THE MINIMUM |
| | BUILDING |
| | TYPE OF CONSTRUCTION. IF THIS SPACE IS TO BE BUILT OUT |
| | AS A TYPE IIB THE BEARING WALLS WILL AS WELL AS |
| | NONBEARING WALLS WILL ALL NEED TO BE FIRE RETARDANT |
| | TREATED WOOD PLEASE SEE TABLE 601 FOOTNOTE C-II . LOOK |
| | AT TABLE 503 UNDER MERCANTILE AT A BUILDING TYPE VB, |
| | THE ALLOWABLE AREA OF 9,000 FOR A SINGLE STORY |
| | BUILDING. IN THIS CATEGORY THE EXTERIOR AND INTERIOR OF |
| | THE BUILDING DOES NOT REQUIRE THE FIRE RETARDANT |
| | TREATED WOOD. |
| | PLEASE PROVIDE : |
| | 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION THAT |
| | IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE OF |
| | OCCUPANCY: |
| | A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT WAS |
| | DESIGNED.NOTE THE BASE CODE IS THE 2004 FBC WITH 2006 |
| | REVISIONS. |
| | ALSO NOTE TO WHAT LEVEL OF ALTERATION IS BEING |
| | COMPLETED UNDER THE 2004 FBC EXISTING BUILDING CODE? |
| | IS THIS A CHANGE IN OCUPANCY? |
| | B) COMPLIED. |
| | C)THE TYPE OF CONSTRUCTION AS DEFINED IN TABLE |
| | 503- MERCANTILE & CHAPTER 6, TABLE 601. |
| | D) COMPLIED. |
| | E) COMPLIED. |
| | F) COMPLIED. |
| | G) SEMI-COMPLIED.SQ. FT. UNDER ROOF (TOTAL) FOR THE |
| | TOTAL BUILDING NOT TENANT SPACE. TENANT SPACE IS ALSO |
| | NEEDED AND PROVIDED. THE REQUIEMENT FOR THE TOTAL BLDG |
| | SQUAREFOOTAGE IS BECAUSE OF THE TYPE II BUILDING |
| | CLASSIFICATION THE DESIGN PROFESSIONAL HAS INDICATED |
| | INACTING THE FIRERETARDANT TREATED WOOD. THIS |
| | BUILDING BEING A ONE STORY BUILDING APPROXIMATELY 3150 |
| | SQ. FT. WILL QUALIFY AS A TYPE V-B. |
| | |
| | 4) 2ND REQUEST,THE PLANS DO NOT INDICATE WHERE THE |
| | PROPERTY LINE WOULD BE OR IF THE FRONT DOOR SWINGS IN |
| | OR OUT OVER THE PROPERTY LINE? AGAIN, IF THE LEVEL OF |
| | ALTERATION PROVIDED UNDER THE 2004 FBC, AND IF THIS IS |
| | A CHANGE OF OCCUPANCY IT MAY OR MAY NOT ENACT CERTAIN |
| | REQUIREMENTS OF THE CODE. 2004 EXISTING BUILDING CODE |
| | SECTION 303 ALL BUILDING ALTERATIONS WILL BE CLASSIFIED |
| | TO ACCORDING TO LEVEL OF ALTERATION. CHANGES IN |
| | OCCUPANCIES MAY OR MAY NOT INACT CODE ISSUES DEPENDING |
| | ON THE CATEGORY OF OCCUPANCY, SEE 2004 EXISTING |
| | BUILDING |
| | CODE IN CHAPTER 8 CHANGE OF OCCUPANCIES. |
| | |
| | 5) COMPLIED. |
| | |
| | 6)2ND REQUEST,PLANS INDICATE A RAMP DIRECTLY INSIDE |
| | THE UNIT WITH NO BOTTOM LANDING.11-4.8.4.(2) |
| | LANDINGS. ALL LANDINGS ON RAMPS SHALL NOT BE LESS THAN |
| | 60" |
| | CLEAR, & THE BOTTOM OF EACH RAMP SHALL HAVE NOT LESS |
| | THAN 72" OF STRAIGHT & LEVEL CLEARENCE. THE PLANS ARE |
| | MISSING THE BOTTOM LANDING OF 72", DEPENDING ON PART OF |
| | THE ANSWER TO COMMENT 3A) ANDCOMMENT# 4THIS |
| | REQUIREMENT MAY NOT HAVE TO BE MET. |
| | |
| | 7) 2ND REQUEST, PLEASE PROVIDE DOOR WIDTH FOR ALL NEW |
| | INTERIOR DOORS. 11-4.13.5 DOORWAYS, MINIMUM CLEAR |
| | WIDTH: DOORWAY SHALL HAVE A MINIMUM CLEAR OPENING OF |
| | 32" WITH THE DOOR OPEN 90 DEGREES, MEASURED BETWEEN THE |
| | FACE OF THE DOOR AND THE OPPOSITE STOP. THE PLANS |
| | INDICATE A 32INCH OPENING TO THE RESTROOM THIS WILL |
| | ONLY WORK IF THE HINGES ARE SWING CLEAR OF OPENING |
| | TYPE OF HINGE, THE DOOR WHEN OPENED 90 DEGRESS WILL |
| | SWING CLEAR OF THE DOOR OPENING OTHERWISE THE MINIMUM |
| | DOOR OPENING SIZE IS A 2'-10" OR 34INCHES. |
| | |
| | 8) 2ND REQUEST, THE RESTROOM DOES NOT PROVIDE |
| | DIMENSIONS, NOR IS THE 5'-0" TURNING CIRCLE INDICATED |
| | FOR THE HANDICAPPED RESTROOM. IT APPEARS THE TOLIET IS |
| | LOCATED IN THE TURNING RADIUS. 11-4.2.3 WHEELCHAIR |
| | TURNING SPACE. THE SPACE REQUIRED FOR A WHEELCHAIR TO |
| | MAKE A 180-DEGREE TURN IS A CLEAR SPACE OF 60 INCHES |
| | (1525 MM) DIAMETER [SEE FIGURE 3 (A)] OR A T-SHAPED |
| | SPACE [SEE FIGURE 3 (B)]. |
| | |
| | 9) IS THIS AGAIN A CHANGE IN OCCUPANCY, AND OR A NEW OR |
| | RECONFIGURED RESTROOM? 11-4.16.2 CLEAR FLOOR SPACE. |
| | WATER CLOSET.CLEAR FLOOR SPACE FOR WATER CLOSETS NOT IN |
| | STALLS SHALL COMPLY WITH FIGURE 28 . CLEAR FLOOR SPACE |
| | MAY BE ARRANGED TO ALLOW EITHER A LEFT-HANDED OR |
| | RIGHT-HANDED APPROACH. |
| | |
| | 10) 2ND REQUEST, THE SIDE GRAB BAR IN THE RESTROOM, |
| | PLEASE DIMENSION THE SIZE AND LOCATION OF THE GRAB BAR. |
| | 11-4.16.4 GRAB BARS.PLEASE SEE FIGURE# 29 FOR LOCATION |
| | AND THE MINIMUM SIZE REQUIREMENTS FOR GRAB BARS. THE |
| | SIDE GRAB BAR IS TO BE A MINIMUM OF 42 INCHES LONG AND |
| | THE LEADING EDGE TO BE AT 54 INCHES FROM THE CORNER. |
| | THE BACK BAR ALSO IS NOT DIMENSIONED FOR LENGTH WHICH |
| | WOULD BE 36" AND ONE END OF THE BACK GRAB BAR BEING 12 |
| | INCHES OF CENTER OF THE WATER CLOSET BEING SET UP FOR A |
| | LEFTOR RIGHT HANDED SIDE APPROACH, SEE FIGURE 29 FOR |
| | CLARIFICATION. |
| | GRAB BARS FOR WATER CLOSETS NOT LOCATED IN STALLS SHALL |
| | COMPLY WITH SECTION 11-4.26 AND FIGURE 29 . THE GRAB |
| | BAR BEHIND THE WATER CLOSET SHALL BE 36 INCHES (915 MM) |
| | MINIMUM. |
| | |
| | 11) COMPLIED. |
| | |
| | 12)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, |
| | IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE |
| | ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | BUILDING PLAN REVIEW II |
| | JIM WITMER C. B. O. |
| | |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |