| Date |
Text |
| 2007-06-20 07:23:18 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. PLANS SHALL BE ROUTED TO THE STATE OF FLORIDA, DEPT. |
| | OF BUSINESS REGULATION, (DBR), DIVISION OF HOTEL AND |
| | RESTAURANT FOOD SERVICE FOR REVIEW. A MINIMUM OF TWO |
| | STAMPED PLANS WITH "TWO PAGE WORKSHEETS" ATTATCHED TO |
| | STAMPED PAGE SHALL BE SUBMITTED FOR REVIEW TO CITY WPB. |
| | SECTION 102.2.1. |
| | |
| | 2. THE GREASE INTERCEPTOR SHALL BE SIZED BY |
| | ENVIRONMENTAL COMPLIANCE. PLEASE CONTACT RODNEY COMPO, |
| | (561) 822-2272,[email protected] OR CALVIN WILLIAMS, |
| | (561) 822-2284 [email protected]. THEIR FAX NUMBER IS |
| | (561) 822-2287. PLEASE INDICATE THEIR DETERMINATION |
| | WHEN RESUBMITTING. ARTICLE III SECTION 90-124. PLEASE |
| | SUBMIT A DETAIL FOR THE GREASE INTERCEPTOR. (SEE |
| | ATTACHED SHEET SHOWING WPB UTILITY STANDARD FOR |
| | INTERCEPTORS). |
| | |
| | 3. ALL SHEETS. THE ADDRESS DOES NOT REFLECT THE ADDRESS |
| | RECORDED ON THE STATE OF FLORIDA DBPR WEBSITE. (SEE |
| | ATTACHED SHEET). PLEASE UPDATE THE DBPR WEBSITE OR THE |
| | TITLE BLOCKS ON EACH SHEET SO THE ADDRESS CORRELATES. |
| | FAC 61G1-16.004(1) & FS 481-2055. |
| | |
| | 4. SHT A-1 EQUIPMENT SCHEDULE ITEM K11 NOT SHOWN ON THE |
| | FLOOR PLAN. PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 5. INDICATE THE OCCUPANCY LOAD AND SEATING ON THE |
| | PLANS. SECTIONS 1004.3 & 1004.7. |
| | |
| | 6. INDICATE CODE REFERENCES THAT THE PLANS HAVE BEEN |
| | DESIGNED TO. FBC-2004 W/2006 AMENDMENTS MINIMUM. |
| | |
| | 7. SHT A-1 TOILET ROOM. THE TURNING AREA SHALL BE |
| | UNOBSTRUCTED AND THE TOILET SHALL NOT BE IN THE TURNING |
| | AREA. SECTION 11-4.22.3. |
| | |
| | 8. SUBMIT A DETAIL FOR THE TOILET ROOM SHOWING |
| | COMPLIANCE WITH SECTIONS 11-4.16, 11-4.19 & 11-4.22 |
| | WITH ALL SUBSECTIONS. THE DETAIL SHALL SHOW THE FLOOR |
| | PLAN AND ELEVATIONS WITH ALL REQUIRED MEASUREMENTS. THE |
| | W/C SHALL BE 18" OFF THE WALL TO THE CENTERLINE OF THE |
| | FIXTURE, AND THE LAV SHALL BE A MINIMUM 15" OFF THE |
| | WALL TO THE CENTERLINE OF THE FIXTURE. SEE FIGS 28 & |
| | 29. |
| | |
| | 9. SUBMIT A FINISH SCHEDULE FOR THE TOILET ROOM SHOWING |
| | COMPLIANCE WITH SECTIONS 1210.1 & 1210.2. WALLS WITHIN |
| | 2 FEET OF THE WATER CLOSET SHALL BE A SMOOTH, HARD AND |
| | NONABSORBENT SURFACE. |
| | |
| | 10. SHT A-2 THE GREASE RISER DIAGRAM DOES NOT REFLECT |
| | THE FIXTURE LAYOUT ON THE FLOOR PLAN. PLEASE SHOW A |
| | PIPING LAYOUT ON THE FLOOR PLAN AND THE GREASE RISER |
| | ISOMETRIC DIAGRAM SHALL REFLECT THE PIPING LAYOUT. |
| | SECTION 106.1.1. |
| | |
| | 11. SHT A-2 SANITARY ISOMETRIC RISER DIAGRAM DOES NOT |
| | CONNECT TO THE BUILDING DRAIN. SHOW THE CONNECTION FOR |
| | THE BRANCH LINE TO THE BUILDING DRAIN . SECTION |
| | 106.1.1. |
| | |
| | 12. SUBMIT A WATER RISER DIAGRAM. SHOW ALL PIPE SIZES, |
| | VALVES, AND WATER HAMMER ATTESTORS, (REQD BY SECTIONS |
| | 604.9). SECTION 106.3.5.1.3(3)(8)(10)(13). |
| | |
| | 13. SUBMIT A WATER HEATER DETAIL SHOWING COMPLIANCE |
| | WITH SECTIONS 503.1, 504.6.1 & 607.3.2 (THERMAL |
| | EXPANSION CONTROL). |
| | |
| | 14. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SERVICE |
| | TO THE SPACE. SECTION 608.13.2. PLEASE INDICATE ON THE |
| | PLANS. |
| | |
| | 15. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING |
| | INFORMATION IS REQUIRED FOR THE GAS PERMIT: |
| | |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE IF BEING USED. |
| | |
| | C. TYPE OF GAS, (LP OR NATURAL). |
| | |
| | D. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | |
| | E. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | |
| | F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | |
| | G. CLEARLY SHOW THE LOCATION AND CAP- |
| | ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, BUILD |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58, TABLE 3-2.2.2. |
| | |
| | H. CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES |
| | PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 3-2.2.7(H). |
| | |
| | I. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |