| 2007-06-16 11:44:25 | ------------------DENIED-------------------- |
| | |
| | FBC 2004 CODE FAMILY W/ 2006 REVISIONS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | |
| | 1. PLEASE SHOW SIZE OF OUTSIDE AIR DUCT FROM 12X12 |
| | O.A.I. TO R/A PLENUM. ALSO, PLEASE SHOW CFM OF 6" DROP |
| | IN BACK OF SPACE. FBC 106.1.1. |
| | |
| | 2. SUPPLY TRUNK LINE SHOWS ONE TRANSITION FROM 1/12 TO |
| | 12/10. IS THE TRUNK LINE TO REMAIN THAT SIZE FOR THE |
| | REMAINING 3 DROPS? FBC 106.1.2. |
| | |
| | 3.PLEASE SHOW VENTILATION CALCULATIONS WHICH |
| | DEMONSTRATE COMPLIANCE WITH FBC,M 403.3. ALSO, BATHROOM |
| | EXHAUST IS ALSO REQUIRED BY THIS SECTION. PLEASE SHOW |
| | MEANS OF EXHAUST, CFM AND DISCHARGE LOCATION. |
| | |
| | 4. PLEASE SHOW AN AIR BALANCE SCHEDULE INCLUDING |
| | SUPPLY, RETURN, OUTSIDE AIR, BATHROOM EXHAUST, KITCHEN |
| | EXHAUST WITH MAKE-UP AIR TO SHOW PRESSURIZATION OF |
| | SPACE PER FBC 13-409.1.ABC.2 AND COMPLIANCE WITH |
| | KITCHEN SPACE REQUIREMENTS OF 13-409-1.ABC 3.6.1. |
| | |
| | 5.PLEASE SHOW MEANS/LOCATION OF CONDENSATE DISPOSAL IN |
| | COMPLIANCE WITH FBC,M 307.2 (ALL SECTIONS) INCLUDING |
| | SECONDARY/AUXILIARY DRAIN PROTECTION PER 307.2.3. |
| | |
| | 6. ELECTRICAL PLAN INDICATES A/C EQUIPMENT IS EXISTING, |
| | BUT SCOPE OF WORK AS DESCRIBED ON PERMIT APPLICATION |
| | STATES "SPACE IS CURRENTLY GUTTED."ALSO, HVAC NOTE #6 |
| | SUGGESTS A/C EQUIPMENT IS NEW, NOT EXISTING. WHICH ONE |
| | IS CORRECT? FBC 106.1.1. |
| | |
| | 7. EQUIPMENT SCHEDULE SHOWS INDOOR AIRFLOW AT 1000 CFM |
| | BUT FLOOR PLAN SHOWS 1300 CFM, NOT INCLUDING THE 6" |
| | DROP WHICH DOESN'T SHOW CFM. PLEASE SHOW CORRELATION |
| | BETWEEN SCHEDULE AND FLOOR PLAN. |
| | |
| | 8. HVAC NOTE #4 IS IN CONFLICT WITH NOTE #9. PLEASE |
| | CLARIFY. |
| | |
| | 9. SCOPE OF WORK ON PERMIT APPLICATION INDICATES GAS |
| | AND KITCHEN EQUIPMENT. PLEASE SHOW ALL VENTS AND |
| | KITCHEN EXHAUST PER FBC 106.3.5.1.4. ALSO, A COMMERCIAL |
| | KITCHEN GREASE EXHAUST VENTILATION SYSTEM W/ AUTOMATIC |
| | FIRE SUPPRESSION SYSTEM IS REQUIRED PER FBC,M 507.2.1 |
| | AND 509.1. |
| | |
| | 10. PLEASE SEE FBC,M 507.9 FOR CLEARANCE REQUIREMENTS |
| | RELATED TO TYPE I KITCHEN HOODS INCLUDING REQUIREMENTS |
| | FOR WALL SURFACES ADJASCENT TO THE HOOD AND COOKING |
| | EQUIPMENT. |
| | |
| | 11. SIGNIFICANT INFORMATION IS MISSING FROM PLANS TO |
| | SHOW A CODE COMPLIANT BUILDING/SPACE AT THIS TIME. |
| | ADDITIONAL COMMENTS ARE POSSIBLE BASED ON THE |
| | ADDITIONAL INFORMATION WHEN IT IS PROVIDED. |
| | |