| 2007-06-08 08:20:10 | *** UNSAT *** |
| | |
| | 1) NOTE:PLEASE STATE ALL OF THE RELEVANT CODES AS |
| | ADOPTED FROM THE STATE OF FLORIDA AS OF DECEMBER 8TH, |
| | 2006. |
| | PLEASE LIST THE FOLLOWING AT A MINIMUM ON ELECTRICAL |
| | SHEETS AS WELL AS ARCHITECTURAL. |
| | 2004 FBC W/2006 REVISIONS. |
| | 2005 NFPA-70 (NEC). |
| | 2003 NFPA-101 (LS CODE). |
| | |
| | 2) NOTE: PLEASE SEE FBC CHAPTER 13 FOR COMPLIANCE FOR |
| | ENERGY CALCULATIONS/PERFORMANCE CALCULATIONS |
| | 13-415.1.AB1.1, 13-415.2. |
| | PLEASE SEE MISSING LIGHTING CONTROLS AS REQUIRED PER |
| | 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| | ** AS NO INFORMATION ON SCHEDULING, TYPEOF DEVICES, |
| | FIXTURES, WATTAGES, OVER RIDES, ETC HAVE BEEN SUBMITTED |
| | FOR REVIEW, COMMENTS CAN NOT BE MADE AT THIS TIME. |
| | |
| | 3) NOTE: PLEASE SEE THE SERVICE AS SHOWN CONTAINS A |
| | NOTE AT THE BOTTOM WHICH INDICATES *EXISTING* YET THE |
| | RISER AS SHOWN INDICATES SOME ITEMS AS *NEW*?? PLEASE |
| | CLARIFY ALL SERVICE EQUIPMENT AS SHOWN. PLEASE SEE THE |
| | PANEL SCHEDULE SHOWS THIS AS A 300AMP PANEL WITH 244 |
| | AMP LOAD, YET THE PANEL IS ONLY BEING FED W/ A 2-POLE |
| | 70AMP BREAKER WITH CONDUCTORS WHICH ARE ONLY RATED AT |
| | 65AMPS?? |
| | PLEASE SEE THE LOAD ON PANEL AS NOTED ABOVE SHOWN AT |
| | 244AMPS, YET THE RISER LOAD CALCULATIONS ARE SHOWN |
| | SUBSTANTIALLY LESS FOR THIS SAME UNIT?? |
| | PLEASE SEE THERE ARE SEVERAL ITEMS INCORRECT WITH THIS |
| | RISER AND NEW FEED TO PANEL. |
| | PLEASE SEE 240, 310, 408, 230, 215.5 ETC. |
| | PLEASE ADJUST ALL. |
| | FBC 106.3.5.1.2 |
| | |
| | 4) NOTE: PLEASE SEE ALL BREAKERS ON THE PANEL SCHEDULE |
| | ARE 1-POLE BREAKERS? HOW IS THIS POSSIBLE FOR THE |
| | 240/220/208 VOLT UNITS. |
| | IS ALL EQUIPMENT ON SINGLE POLE BREAKERS? |
| | PLEASE SEE NEC. |
| | |
| | 5) NOTE: PLEASE SEE THE AHU SEEMS TO BE SHOWN WITH 10KW |
| | LOAD YET THE CONDUCTOR AND BREAKER SIZE IS NOT |
| | SUFFICIENT PER CODE. |
| | PLEASE SEE 240.4, 310.16, 424.3B. |
| | |
| | 6) NOTE: PLEASE CLARIFY WATER HEATER AS PLANS INDICATES |
| | A STORAGE TYPE UNIT AND PANEL SCHEDULE INDICATES |
| | INSTANT TYPE HEATERS. |
| | PLEASE SEE 422.13 AND THE FOLLOWING COMMENT FOR LOAD |
| | CALCULATIONS. |
| | |
| | 7) NOTE: PLEASE SUBMIT COMPLETE LOAD CALCULATIONS ON |
| | THE NEW PROPOSED LOAD FOR THIS TENANT SPACE AND FOR THE |
| | ENTIRE SERVICE FOR EXISTING LOADS AND NEW LOADS BEING |
| | ADDED TO SERVICE. THE LOAD AS SHOWN ON THE RISER LOAD |
| | CALCULATIONS IS NOT POSSIBLE. |
| | PLEASE SEE NEC 220 (ALL), 215.3, 230.42. |
| | PLEASE BE SURE ALL CONTINUOUS LOADS ARE SHOWN AT 125% |
| | |
| | 8) NOTE: PLEASE SEE THE SHOW WINDOW RECEPTACLE IS BEING |
| | SHOWN ON THE GENERAL RECEPTACLE CIRCUIT WHICH IS NOT |
| | PERMITTED. |
| | 210.62,220.14, 220.44. |
| | |
| | 9) NOTE: PLEASE SEE THE PLANS INDICATE SOME SORT OF |
| | REFRIGERATOR AT THE FRONT ENTRANCE WHICH IS BEING SHOWN |
| | ON THE SAME GENERAL RECEPTACLE CIRCUIT AS SHOW WINDOW |
| | ETC. PLEASE SEE THE VA ON UNIT NEEDS TO BE VERIFIED AS |
| | THE CIRCUIT MOST LIKELY WILL NEED TO BE DEDICATED. |
| | PLEASE KNOW AS THE LOADS ARE NOT SHOWN, DETERMINATION |
| | CAN NOT BE DONE AT THIS TIME. |
| | PLEASE SEE 430, 422, 422, 220 ETC. |
| | FBC 106.1.2 |
| | |
| | 10) NOTE: PLEASE SEE 210.8B2 FOR ALL REQUIRED GFI |
| | PROTECTED CIRCUITS/RECEPTACLES ON PLANS IN KITCHEN FOOD |
| | PREP AREAS AND THE LIKE. |
| | |
| | 11) NOTE: PLEASE SEE VALUE FOR SCOPE OF WORK IS TO |
| | INCLUDE ALL LABOR, MATERIALS, EQUIPMENT, DESIGN COST |
| | ETC., EVEN IF ANY OF THESE ARE OWNER SUPPLIED. PLEASE |
| | SEE FBC 108.3. |
| | |
| | 12) NOTE: PLEASE SEE CU IS BEING SHOWN ON 1-POLE |
| | CIRCUIT? |
| | |
| | 13) NOTE: PLEASE COMPLETE CIRCUITING ON PLANS AND |
| | COORDINATE WITH THE SUBMITTED PANEL SCHEDULE. PLEASE |
| | SEE SOME ELECTRICAL ITEMS NOT SHOWING CIRCUITS. PLEASE |
| | ALSO SEE 700.12F FOR CIRCUITING OF EM/EXT LTS. |
| | |
| | 14) NOTE: PLEASE INDICATE THE SUITE/UNIT NUMBER ON |
| | PLANS/ TITLE BLOCKS. |
| | FAC 61G1-16.004 FBC 106.1.2 |
| | |
| | 15) NOTE: PLEASE SEE THE PANEL SCHEDULE INDICATES |
| | SEVERAL ITEMS BEING EXISTING, HOWEVER AS THIS IS A NEW |
| | BUILD-OUT FROM PREVIOUS SHELL THIS IS NOT POSSIBLE. |
| | PLEASE ADJUST. 408.4. |
| | FBC 106.3.5.1.2 |
| | |
| | |
| | ** PLEASE KNOW AT THIS TIME AS SOME OF THE INSTALLATION |
| | IS NOT CLEAR, THERE MAY BE COMMENTS IF THE INSTALLATION |
| | CHANGES AND/OR PERMIT APPLICATION CHANGES. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-06-08 07:35:12 | IN ELEC FOR REVIEW |