| 2007-08-22 11:20:09 | *** REDLINED NOTES ON PLANS. | | | | | | | | | PERMIT IS ISSUED BASED ON THE ATTACHED ORIGINAL LETTER | | | FROM OWNER/CEO/PRESIDENT/OFFICER STATING THAT THE | | | CONNECTION AND DISCONNECTION OF ANY GENERATOR BACK UP | | | POWER WILL ONLY BE DONE BY *QUALIFIED PERSONNEL* AS | | | DEFINED IN THE NATIONAL ELECTRICAL CODE. THE | | | INSTALLATION OF *KEYED INTERLOCK* BREAKERS AS SHOWN ON | | | PLANS ONLY MEETS THE *EXCEPTION* OF 702.6 AND THIS | | | REVIEWER UNDER RIGHTS TO INTERPRETATION IN FS 468.619 | | | IS NOT ISSUING PERMIT BASED ON MEETING 702.6.THE | | | KEYED INTERLOCK DOES NOT PROVIDE INADVERTENT CONNECTION | | | OF BOTH THE UTILITY AND BACK UP POWER SOURCE BASED ON | | | THE FACT THAT MULTIPLE KEYS ARE READILY AVAILABLE FROM | | | MANUFACTURE(S) AND KEYED LOCK MANUFACTURE(S). | | | THE RULING FROM LAW DEPARTMENT , THE BUILDING OFFICIAL, | | | ASSISTANT BUILDING OFFICIAL, CHIEF ELECTRICAL INSPECTOR | | | AND THIS REVIEWER IS BASED ON THE EXCEPTION IN 702.6 | | | THAT ALLOWS THEWORK IS ONLY DONE BY*QUALIFIED | | | PERSONNEL* . | | | ***** ANY VIOLATION OFMULTIPLE KEYS, ANY IMPROPER | | | OPERATION OF EQUIPMENT, CORRECT SIGNAGE AND WORK DONE | | | BY UN-QUALIFIED PERSONNEL COULD RESULT IN DEATH AND/OR | | | SERIOUS INJURY, PROPERTY AND FIRE DAMAGE. |
|