| Plan Review Notes For Permit 07050620 |
| Permit Number |
07050620 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-07-23 11:08:58 | *** UNSAT *** | | | | | | 1) NOTE: PLEASE SEE THE PLANS WERE SUBMITTED BACK | | | WITHOUT THE REQUIRED MANUFACTURES SPECS/CUT SHEETS FOR | | | THE SERVICE EQUIPMENT BEING PROPOSED. | | | PLEASE SUBMIT THIS. | | | 110.3, 90.7, | | | FBC 106.1.2 | | | | | | 2) NOTE: PLEASE SUBMIT A SIGNED, NOTARIZED LETTER FOR | | | VERIFICATION THAT THE INSTALLATION AND HOOK UP AND | | | DISCONNECTING OF THE *PORTABLE GENERATOR* WILL ONLY BE | | | DONE BY *QUALIFIED PERSONNEL* AS DEFINED IN THENEC | | | 702.6, AND 100. | | | PLEASE KNOW THIS LETTER NEEDS TO BE FROM ONE OF THE | | | OWNERS/OFFICERS OF THE COMPANY CORPORATION. | | | THIS DETERMINATION FOR THE REQUIRED DOCUMENTATION IS BY | | | THIS REVIEWER, ASSISTANT BUILDING OFFICIAL AND BUILDING | | | OFFICIAL IF A *KIRK KEY* IS BEING USED OR PROPOSED. | | | PLEASE SEE THE RISER STILL INDICATE THIS AS A MTS, | | | PLEASE KNOW THIS HAS YET TO BE VERIFIED FOR LISTING A | | | MTS. | | | | | | | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|