2008-06-23 12:08:35PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 REVISION TO MECHANICAL PLAN M.1.
 *** DENIED ***
  
 1) NOTED IN LAST REVIEW 6-13-08 NOTE #1. ENERGY
 CALCULATION ON FILE ARE CALLING FOR 14 SEER (MIS-TYPED
 13 SEER IN LAST REVIEW) A/C SYSTEMS, A/C SYSTEM #3 ON
 REVISED MECHANICAL PLAN IS A 13 SEER. PLEASE CORRECT
 (MAY NEED TO REVISE ENERGY CALCULATIONS) PER 2004 FBC
 13-103.3.
  
 2) NOTED IN LAST REVIEW 6-13-08 NOTE #2. A/C SYSTEMS 1
 AND 2 MODEL NUMBERS ARE NOT CORRECT (SEE ATTACHED ARI
 CERTIFICATES). PLEASE SUBMIT ARI CERTIFICATES FOR A/C
 SYSTEMS ANDCORRECT EQUIPMENT SCHEDULE, PER 2004 FBC
 106.3.5.
  
 2A) IF THE ATTACHED ARI CERTIFICATE FOR SYSTEM 2 IS THE
 SYSTEM BEING INSTALLED PLEASE CORRECT THE SEER AND
 TOTAL COOLING BTU'S IN THE EQUIPMENT SCHEDULE ON
 MECHANICAL PLAN.
  
 3) NOTED IN LAST REVIEW 6-13-08 NOTE #3. THE COOLING
 LOAD CALCULATIONS ON FILE (SEE ATTACHED COPY) ARE
 CALLING FOR 66,423 TOTAL COOLING BTU'S, THE REVISED
 MECHANICAL PLAN EQUIPMENT SCHEDULE TOTALS 89,800 TOTAL
 COOLING BTU'S, THE PLANS CAN ONLY CALL FOR 15% MORE
 TOTAL COOLING BTU'S THAN THE COOLING LOAD CALCULATIONS
 PER 2004 FBC 13-607.1.ABC.1.1. PLEASE CORRECT PLANS OR
 REVISE COOLING LOAD CALCULATIONS WITH ZONES FOR EACH
 SYSTEM.
  