Plan Review Notes
Plan Review Notes For Permit 07050618
Permit Number 07050618
Review Stop E
Sequence Number 4
Notes
Date Text
2008-06-12 12:03:15 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1
 AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE RISER INDICATES A METER/MAIN, THE FLOOR PLAN
 SHOWS A METER ONLY. CORRELATE TO SHOW ACTUAL
 INSTALLATION.106.1.1 FBC AS AMENDED.
  
 2} GEC FROM PANEL "H" MUST NOT BE INSTALLED AS IT
 PARALLELS THE EQUIPMENT GROUND IN VIOLATION OF 250.6.
  
 3} THERE HAVE BEEN NO ELECTRICALREVISIONS SINCE THE
 PERMIT SET WAS REVIEWED. THE ENTIRE HOUSE APPEARS TO
 HAVE BEEN REWIRED.. NO CLOUDS ARE ON THE PLAN
 INDICATING REVISIONS 2,3 AND 4, THEREFORE WHAT IS PART
 OF THIS PERMIT CANNOT BE KNOWN OR REVIEWED. CLOUD THE
 REVISIONS OR INDICATE THE CHANGES THAT APPLY TO THIS
 PERMIT.
  
 4} ADJUST THE VALUE TO REFLECT THE ADDED LABOR AND
 MATERIAL AT THE PERMIT CLERK?S DESK, AND PAY THE
 DIFFERENCE IN FEES PRIOR TO RESUBMITTING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718