| Plan Review Notes For Permit 07050618 |
| Permit Number |
07050618 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2008-06-12 12:03:15 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | | CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1 | | | AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} THE RISER INDICATES A METER/MAIN, THE FLOOR PLAN | | | SHOWS A METER ONLY. CORRELATE TO SHOW ACTUAL | | | INSTALLATION.106.1.1 FBC AS AMENDED. | | | | | | 2} GEC FROM PANEL "H" MUST NOT BE INSTALLED AS IT | | | PARALLELS THE EQUIPMENT GROUND IN VIOLATION OF 250.6. | | | | | | 3} THERE HAVE BEEN NO ELECTRICALREVISIONS SINCE THE | | | PERMIT SET WAS REVIEWED. THE ENTIRE HOUSE APPEARS TO | | | HAVE BEEN REWIRED.. NO CLOUDS ARE ON THE PLAN | | | INDICATING REVISIONS 2,3 AND 4, THEREFORE WHAT IS PART | | | OF THIS PERMIT CANNOT BE KNOWN OR REVIEWED. CLOUD THE | | | REVISIONS OR INDICATE THE CHANGES THAT APPLY TO THIS | | | PERMIT. | | | | | | 4} ADJUST THE VALUE TO REFLECT THE ADDED LABOR AND | | | MATERIAL AT THE PERMIT CLERK?S DESK, AND PAY THE | | | DIFFERENCE IN FEES PRIOR TO RESUBMITTING. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|