Plan Review Notes For Permit 07050618
Permit Number 07050618
Review Stop P
Sequence Number 3
Notes
Date Text
2008-07-21 15:22:03PLUMBING PLAN REVIEW:
 REVISION DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET P.1 IS INDICATING THE WRONG REVISION NUMBER
 3. THAT REVISION NUMBER IS DATED 10/30/07 WHICH IS
 BEFORE PLANS WERE PERMITTED. I THINK THE CORRECT
 REVISION NUMBER SHOULD BE 7. PLEASE CLARIFY, CORRECT,
 AND CORRELATE THIS REVISION. PER THE FOLLOWING "ALL
 CHANGES TO THE PLAN ARE TO BE CLOUDED WITH REVISION
 NUMBERS/DATES PER FBC-2004 CHAPTER 1, SECTION 106.1.3
 THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM.
 NOTE: A TRANSMITTAL LETTER IS HELPFUL."
  
 2. SHEET P.1 PLUMBING FLOOR PLAN HAS THE INCORRECT
 SIZE OF THE CLEANOUT FOR THE WASHING MACHINE INDICATED
 AS BEING 2 INCH. THE CORRECT SIZE OF THIS CLEANOUT IS 3
 INCH. PER FBC- PLUMBING SECTION 708.7 MINIMUM SIZE.
  
 3. SHEET P.1 SANITARY RISER DIAGRAM: THE TWO
 LAVATORIES ARE NOT BEING IDENTIFIED IN MASTER BATH #113
 ON THE RISER DIAGRAM. PER FBC- PLUMBING SECTION 401.1
 AND 701.1 SCOPE.
  
 4. SHEET P.1 SANITARY RISER DIAGRAM: THE REVISION WITH
 THE VENT THRU WALL INSTEAD OF THRU THE ROOF NEEDS
 CLARIFICATION. A PLUMBING INSPECTION DATED 6/25/08
 INDICATED REVISION REQUIRED, THAT AN AIR ADMITTANCE
 VALVE WAS INSTALLED ON THE OUTSIDE BLOCK WALL INSTEAD
 OF A VENT THRU ROOF. THE SUBMITTED PLUMBING REVISION
 DOES NOT INDICATE AN AIR ADMITTANCE VALVE. THE REVISION
 INDICATES A VENT THRU WALL WHICH NEEDS TO HAVE THE
 FOLLOWING INDICATED ON THE PLANS BEFORE IT IS
 COMPLIANT. PER FBC- PLUMBING SECTION 904.6 EXTENSION
 THROUGH THE WALL. VENT TERMINALS EXTENDING THROUGH THE
 WALL SHALL TERMINATE A MINIMUM OF 10 FEET (3048 MM)
 FROM THE LOT LINE AND 10 FEET (3048 MM) ABOVE AVERAGE
 GROUND LEVEL. VENT TERMINALS SHALL NOT TERMINATE UNDER
 THE OVERHANG OF A STRUCTURE WITH SOFFIT VENTS. SIDE
 WALL VENT TERMINALS SHALL BE PROTECTED TO PREVENT BIRDS
 OR RODENTS FROM ENTERING OR BLOCKING THE VENT OPENING.
 NOTE: IF AN AIR ADMITTANCE VALVE IS BEING INSTALLED
 PLEASE INDICATE THAT THIS VALVE WILL BE PROTECTED FROM
 HARMFULL ULTRA-VIOLET (UV) SUN RAYS PER MANUFACTURER'S
 RECOMMENDATIONS.
 ALSO THE VENT CAN NOT BE INSTALLED WITHOUT A VERICAL
 RISE ABOVE THE FLOOD LEVEL RIM OF THE LAVATORY PER FBC-
 PLUMBING SECTION 905.4 VERTICAL RISE OF VENT. EVERY DRY
 VENT SHALL RISE VERTICALLY TO A MINIMUM OF 6 INCHES
 (152 MM) ABOVE THE FLOOD LEVEL RIM OF THE HIGHEST TRAP
 OR TRAPPED FIXTURE BEING VENTED. THE SUBMITTED REVISION
 ON THE PLANS DO NOT INDICATE THIS REQUIREMENT. THE
 SUBMITTED REVISION INDICATES A HORIZONTAL DRY VENT WITH
 NO VERTICAL RISE AS REQUIRED.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]