2008-06-13 08:28:07PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 REVISION TO MECHANICAL PLAN M.1.
 *** DENIED ***
  
 1) ENERGY CALCULATION ON FILE ARE CALLING FOR 14 SEER
 A/C SYSTEMS, A/C SYSTEM #3 ON REVISED MECHANICAL PLAN
 IS A 13 SEER (SEE ATTACHED ARI CERTIFICATE). PLEASE
 CORRECT PER 2004 FBC 13-103.3.
  
 2) AIR HANDLERS #1 AND #2 MODEL NUMBERS ARE NOT
 COMPLETE (SEE RED LINE ON PLAN) THEY MUST INCLUDE THE
 COIL AS MULTIPLE COILS MAY BE INSTALLED IN THE AIR
 HANDLER. PLEASE CORRECT PER 2004 FBC 106.3.5.
  
 3) THE COOLING LOAD CALCULATIONS ON FILE ARE CALLING
 FOR 66,423 TOTAL COOLING BTU'S, THE REVISED MECHANICAL
 PLAN EQUIPMENT SCHEDULE TOTALS 89,600 TOTAL COOLING
 BTU'S, THE PLANS CAN ONLY CALL FOR 15% MORE TOTAL
 COOLING BTU'S THAN THE COOLING LOAD CALCULATIONS PER
 2004 FBC 13-607.1.ABC.1.1. PLEASE CORRECT PLANS OR
 REVISE COOLING LOAD CALCULATIONS.
  
 MECHANICAL PLAN REVIEW BY;