2007-08-15 12:08:01RESIDENTIAL ADDITION BUILDING REVIEW SECOND CHECKLIST:
 REVIEW DONE UNDER 2004 FLORIDA RESIDENTIAL CODE AND FBC
 2004 WITH 2006 REVISIONS.
  
 1- NEED TO ADDRESS ZONING COMMENTS REGARDING SETBACKS.
 PLANS REVISIONS MAY BE REQUIRED. SEE ZONINGCOMMENTS.
  
 2- PER SEC. 713.13 FLORIDA STATUTE NOTICE OF
 COMMENCEMENT EXPIRES AFTER 90 DAYS OF RECORDING IF WORK
 IS NOT STARTED. NOC EXPIRES ON 8-15-07. WILL NEED TO
 PROVIDE RE- RECORDED NOTICE OF COMMENCEMENT.
  
 3- PROVIDE COPY OF IMPACT FEES PAID RECEIPT AS
 REQUESTED ON PREVIOUS CHECKLIST.
  
 4- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) GARAGE DOORS THAT MATCH DOORS SHOWN ON
 ARCHITECTURAL ELEVATIONS AS REQUESTED ON PREVIOUS
 CHECKLIST.
 IN ADDITION BASE ON INFORMATION SUBMITTED THE FOLLOWING
 ITEMS NEED TO BE ADDRESSED:
 (1)FLORIDA PRODUCT APPROVAL FL 4307AND NOA
 03-0213.15 SUBMITTED DON'T CORRESPOND TO EACH OTHER.
 THESE ARE TWO DIFFERENT PRODUCT APPROVALS. PROVIDE
 COMPLETE INFORMATIONEITHERFOR THE FLORIDA PRODUCT
 APPROVAL OR THE DADE COUNTY PRODUCT APPROVAL. ARCHITECT
 APPROVED THE FLORIDA PRODUCT APPROVAL COVER PAGE , BUT
 THERE ARE NOT DRAWINGS SHOWING WHICH MODEL HE APPROVED.
 HOW HE KNOWS THE PRODUCT APPROVAL IS GOOD FOR THE
 CALCULATED DESIGN PRESSURES?
  
 (2) NEED THE NAME OF PERSON APPROVING THE PRODUCT
 APPROVAL.WRITING"APPROVED"ON THE PRODUCT
 APPROVAL IS NOT ENOUGH INFORMATIONBECAUSE IT DOESN'T
 IDENTIFYTHE PERSON OR COMPANY APPROVING THE PRODUCT
 APPROVAL. TYPICALLY THE STANDARD SHOP DRAWINGS REVIEW
 STAMP WITH THE LOGO OR NAME OF THE COMPANY IS USED AND
 IS ACCEPTABLE TO COMPLY WITH THIS SECTION.
  
 B) METAL ROOF AT NEW CUPOLA REQUESTED ON PREVIOUS
 CHECKLIST.
 NOTE: MAKE SURE PRODUCT APPROVAL MEETS THE DESIGN
 PRESSURES OF TABLE 1609.6.2.1(2) FBC 2004 FOR ZONES 2
 AND 3.
  
 C) WINDOW MULLIONS REQUESTED ON PREVIOUS CHECKLIST.
  
 D) SINGLE HUNG WINDOWS.
 BASED ON INFORMATION SUBMITTED THE FOLLOWING IS
 REQUIRED:
 (1) FLORIDA PRODUCT APPROVAL FL7938 AND NOA
 02-0719.05 DON'T CORRESPOND TO EACH OTHER.PROVIDE
 PRODUCT APPROVAL FOR EITHER ONE, BUT DON'T MISMATCH ONE
 WITH THE OTHER.
  
 (2) ARCHITECT'S PLANS CALL FOR WINDOWS WITH
 HURRICANE MISSILE IMPACT GLAZING. FLORIDA PRODUCT
 APPROVAL FL7938 IS NOT FOR IMPACT GLAZING AND THIS IS
 THE ONE THAT ARCHITECT APPROVED. WHY?
  
 E) EXTERIOR SWINGING DOORS:INFORMATION SUBMITTED
 REQUIRES THE FOLLOWING:
 (1) FLORIDA PRODUCT APPROVAL FL253 AND NOA
 05-0103.03 DON'T CORRESPOND TO EACH OTHER. THESE ARE
 TWO DIFFERENT PRODUCT APPROVALS. NEED TO SUBMIT
 COMPLETE INFORMATION FOR EITHER ONE.
  
 (2) FL253-R0DOESN'T HAVE ANY DRAWINGS AND IS FOR
 CODE VERSION 2001.NEED TO PROVIDE 2004 CODE VERSION.
 ARCHITECT TO MAKE SURE CORRECT CODE EDITION IS USED
 PRIOR TO APPROVAL.
  
 5- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 106.3.3 CITY
 AMENDMENTS TO FBC 2004. MAKE SURE NAME OR ARCHITECT OR
 COMPANY NAME IS INCLUDEDTO VERIFYTHAT DESIGNER OF
 RECORD IS THE ONE APPROVING THE PRODUCT APPROVALS.
  
 6- PROVIDE COMPLETE SPECS FOR BBQ GRILL AS REQUESTED ON
 PREVIOUS CHECKLIST.
 NOTE:MAKE SURE BBQ GRILL IS DESIGNED FOR INSTALLATION
 IN PORCH AS SPECIFIED ON PLANS. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 7- ARCHITECT TO SPECIFY ROOF TILE FASTENING AS REQUIRED
 BY BY SEC. 106.1.1.2CITY AMENDMENTS TO FBC 2004. NEW
 DETAIL SUBMITTED ONLY IDENTIFIES RIDGE INSTALLATION,
 WHICH IS REQUIRED BY RAS 118.IT DOESN'T SPECIFY HOW
 ARE THE RESTOF TILES INSTALLED. IT'S GOING TO BE
 POLYPRO ADHESIVE OR NAILS OR SCREWS. IF USING NAILS OR
 SCREWS, THEN SPECIFY SIZE AND NUMBER. IF USING POLYPRO,
 THEN PROVIDE PRODUCT APPROVAL.
  
 8- SPECIFY ATTIC VENTILATION AT NEW CUPOLA AS REQUIRED
 BY SEC. R806 OF 2004 FLORIDA RESIDENTIAL CODE .EVEN
 THOUGH THE CUPOLA IS DECORATIVE, STILL VENTILATION IS
 REQUIRED. THERE ARE NOT EXCEPTIONS IN THE CODE.
  
 9- SPECIFY ALL LIVE AND DEAD LOADS, INCLUDING ATTIC
 LIVE LOADS AS REQUIRED BY TABLE R301.5 OF 2004 FLORIDA
 RESIDENTIAL CODE. ARCHITECT'S RESPONSE LETTER SAID "SEE
 REVISIONS TO SHEET S.3". THERE ARE NOT REVISIONS
 SHOWING THE LOADS ON SHEET S.3.
 IN ADDITION REVISE NOTE D4 ON SHEET S.1 TO INCLUDE ALL
 LOADS INCLUDING THE ATTIC LIVE LOAD.
  
 10- SOIL TEST REPORT PROVIDED REQUIRES THE FOLLOWING:
 A) ENGINEER'S ORIGINAL SIGNATURE AS REQUIRED BY
 CHAPTER 471 FLORIDA STATUTE AND SEC. 61G15-23.002 OF
 FLORIDA ADMINISTRATIVE CODE. REPORT SUBMITTED HAVE COPY
 OF THE SIGNATURE.
  
 B) REPORT NEEDS TO HAVE THE FIRM'S CERTIFICATE OF
 AUTHORIZATION NUMBER AS REQUIRED BY SEC. 61G15-23.002
 OF FLORIDA ADMINISTRATIVE CODE.
  
 11- COORDINATE FOOTING SIZE SHOWN ON DETAIL1/S.2 WITH
 FOOTING SCHEDULE TO MATCH.SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 12- COORDINATE LINTEL SCHEDULE WITH OPENING SIZE SHOWN
 ON PLANS. EG:CHECK LINTEL L3 IN DINING ROOM AREA.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 13- PROVIDE COMPLETE DETAIL/SPECS FOR SOFFIT
 CONSTRUCTION. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
 DETAIL4/S.3 DOESN'T IDENTIFY SOFFIT CONTRUCTION.IF
 USING STUCCO SEE ASTM C926 AND ASTM C1063 TO GET PROPER
 INFORMATION.
 ALSO, THERE ARE NOT SPECS FOR CEILING INSTALLATION AT
 MASTER BEDROOM AND ENTRY PORCH. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 14- SHEET A.1:
 A) KEY LEGEND AND FIRE RATING AND LIFE SAFETY NOTES
 DON'T MATCH. REVISE AS REQUIRED.
  
 B) EGRESS NOTE #2 CALLS FOR OPENING "MIN 22" WIDE OR
 24" HIGH" IS INCORRECT.IT CAN'T BE ONE OR THE OTHER.
 IT MUST MEET BOTH MINIMUM DIMENSIONS. SEE SEC. R310 OF
 2004 FLORIDA RESIDENTIAL CODE AND REVISE NOTE AS
 REQUIRED.
  
 C) CLARIFY NOTE #3. WHERE IS THIS INFORMATION TAKEN
 FROM?SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 15- ALL EXTERIOR ELEVATIONS,SECTION4/A.6, SECTIONS
 ON SHEET A.7AND A.8,AND SEC. 2 /S.3 CALL FOR 5/8"
 ROOF SHEATHING. SPECIFICATION PS-1 ON SHEET S.1
 CALLS FOR 3/4"ROOF SHEATHING. REVISE AS REQUIRED TO
 MATCH. SEC. 106.1.2CITY AMENDMENTS TO FBC 2004.
  
 16- SHEET S.2:
 A) NEW TYP. COLUMN CONNECTOR DETAIL: SIZE OF WEDGE
 ANCHOR SPECIFIED ON SECTION DOESN'T MATCH SIZE
 SPECIFIED ON STEEL PLATE PLAN. REVISE AS REQUIRED TO
 MATCH.
  
 B) SPECIFY COLUMNS AT ENTRY PORCH. THEY ARE SHOWN
 BIGGER THAN THE 8"COLUMN SPECIFIED FOR BREEZEWAY.
  
 17-SHEET S.3:
 A) SPECIFY CONNECTORS AT TOP OF WOOD COLUMNS AT
 CORNER AREAS SHOWING HOW ARE WOOD BEAMS COMING FROM 2
 DIFFERENT DIRECTIONSARE CONNECTED.SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 B) SPECIFY END CONNECTORSFOR WOOD BEAMS AT MASTER
 BEDROOM AND ENTRY PORCH SHOWING HOW ARE BEAMS SUPPORTED
 ON MASONRY WALL. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004
  
 C) CONNECTION SCHEDULE:
 (1) SIMPSON STRAP LTS18 IS NOT DESIGNED TO PROVIDE
 LATERAL SUPPORT. WHERE IS THE 200# TAKEN FROM? AND WHAT
 LATERAL LOAD (PERPENDICULAR OR PARALLEL) IS THIS NUMBER
 FOR?SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 (2) SPECIFY BOTH LATERAL LOADS FOR WHICHSIMPSON
 HETA20 IS DESIGNED FOR. SEE SIMPSON CATALOG.
  
 (3) WHERE IS UPLIFT LOAD FOR SIMPSON HETA20 TAKEN
 FROM?. IT DOESN'T MATCH UPLIFT LOAD TESTED AND
 PUBLISHED BY THE MANUFACTURER. SEE CURRENT CATALOG AND
 REVISE AS REQUIRED.
  
 (4) CONNECTOR SPECIFIED ON SECTION 2 DOESN'T MATCH
 CONNECTION SCHEDULE. REVISE AS REQUIRED.
  
 (5) SECTION 2 DOESN'T MATCH SECTION 4/A.7.THERE
 ARE TWO ADDITIONALTOP PLATES SPECIFIED ON DETAIL
 4/A.7. REVISE AS REQUIRED TO MATCH.
  
 (6) SIZE OF POST SPECIFIED ON DETAIL 2/S.3 DOESN'T
 MATCH SIZE SPECIFIED ON FOUNDATION PLAN. REVISE AS
 REQUIRED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER