| 2007-06-08 15:24:54 | DENIED |
| | REFERENCE: |
| | ** FBC-2004 PLUMBING. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FLORIDA ADMINISTRATIVE CODE. |
| | ** FLORIDA STATUTES. |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1. SHEET P.1 SANITARY ISOMETRIC RISER DIAGRAM: THE |
| | FOLLOWING IS REQUIRED AND NEEDS TO BE INDICATED ON THE |
| | DRAWINGS FOR THE WASHING MACHINE PER FBC-2004 |
| | PLUMBING. |
| | (A) 406.3 WASTE CONNECTIONS.THE TRAP AND |
| | FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES |
| | WASHER SHALL BE A MINIMUM OF 2 INCHES |
| | (51MM) IN DIAMETER. THE AUTOMATIC |
| | CLOTHES WASHER FIXTURE DRAIN SHALL |
| | CONNECT TO A BRANCH DRAIN OR DRAINAGE |
| | STACK A MINIMUM OF 3 INCHES (76MM) IN |
| | DIAMETER. |
| | NOTE: THE WASHING MACHINE BRANCH AND STACK DRAIN ARE |
| | SIZED WRONG ON THE ISOMETRIC. PLEASE CORRECT ON THE |
| | RESUBMITTAL. |
| | |
| | (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY |
| | TRAPPED. STANDPIPES SHALL |
| | EXTEND A MINIMUM OF 18 INCHES (457MM) |
| | AND A MAXIMUM OF 42 INCHES (1066MM) |
| | ABOVE THE TRAP WEIR. ACCESS SHALL BE |
| | PROVIDED TO ALL STANDPIPES AND DRAINS |
| | FOR RODDING. PLEASE INDICATE THE STANDPIPE ON THE |
| | RESUBMITTAL. |
| | |
| | (C) 708.7 MINIMUM SIZE. CLEANOUTS SHALL |
| | BE THE SAME NOMINAL SIZE AS THE PIPE |
| | THEY SERVE UP TO 4 INCHES (102MM). |
| | NOTE: CLEANOUT FOR THE WASHING MACHINE SHALL BE THREE |
| | INCH (3"). PLEASE INDICATE THIS ON THE RESUBMITTAL. |
| | |
| | (D) 708.9 ACCESS. ACCESS SHALL BE |
| | PROVIDED TO ALL CLEANOUTS. |
| | NOTE: CLEANOUT FOR THE WASHING MACHINE TO BE LOCATED AT |
| | FOUR FEET ABOVE FINNISH FLOOR (4' A.F.F.). PLEASE |
| | INDICATE THIS ON THE RESUBMITTAL. |
| | |
| | 2. SHEET P.1 SANITARY ISOMETRIC RISER DIAGRAM: THE LAV |
| | IN ROOM 114 IS DRAWN WRONG AND DOES NOT REFLECT THE |
| | PLUMBING FLOOR PLAN. PLEASE CORRECT ON THE |
| | RESUBMITTAL. |
| | |
| | 3. SHEET P.1 SANITARY ISOMETRIC RISER DIAGRAM: THE |
| | ISOMETRIC DOES NOT REFLECT THE PLUMBING FLOOR PLAN FROM |
| | THE BUILDING SEWER TO THE MASTER BATH AND ALSO TO THE |
| | LAVS IN MASTER BATH ROOM #113. PLEASE CORRECT ON THE |
| | RESUBMITTAL. |
| | |
| | 4. SHEET P.1 SANITARY ISOMETRIC RISER DIAGRAM AND |
| | PLUMBING FLOOR PLAN: MASTER BATH ROOM #113 A VENT IS |
| | REQUIRED FOR THE SHOWER PER TABLE 906.1 A 2" TRAP CAN |
| | ONLY BE 6' FROM VENT. PLEASE CORRECT ON THE |
| | RESUBMITTAL. |
| | |
| | 5. SHEET P.1 SANITARY ISOMETRIC RISER DIAGRAM AND |
| | PLUMBING FLOOR PLAN: PLEASE SEE RED LINE CORRECTIONS TO |
| | THE TWO-WAY CLEANOUTS IN THREE PLACES. |
| | |
| | 6. SHEET P.1 PLUMBING NOTE NUMBER SEVEN (7): PLEASE |
| | DELETE THE FOLLOWING "FURNISH AND INSTALL APPROVED |
| | SHOCK ABSORBERS AT EACH PLUMBING FIXTURE GROUP" AND |
| | PLEASE ADD THE FOLLOWING "PER FBC-2004 PLUMBING, |
| | SECTION 604.9 A WATER-HAMMER ARRESTOR SHALL BE |
| | INSTALLED WHERE QUICK-CLOSING VALVES ARE UTILZED AND |
| | SHALL BE INSTALLED IN ACORDANCE WITH THE MANUFACTURER'S |
| | SPECIFICATIONS." |
| | |
| | 7. SHEET P.1 PLUMBING FLOOR PLAN IS INDICATING A GAS |
| | WATER HEATER AND A GAS STUB W/ SHUTOFF IN THE PROPOSED |
| | COVERED PATIO AREA. A SEPERATE GAS PERMIT IS REQUIRED |
| | FOR THIS WORK. PLEASE PROVIDE THE FOLLOWING INFORMATION |
| | FOR THE GAS PERMIT. |
| | |
| | A} SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | |
| | B} SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | |
| | C} TYPE OF GAS, (LP OR NATURAL). |
| | |
| | D} BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). |
| | |
| | E} SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | |
| | F} INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | |
| | G} SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | |
| | H} CLEARLY SHOW THE LOCATION AND CAP- |
| | ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, BUILD |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58, TABLE 3-2.2.2. |
| | |
| | I} CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES |
| | PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 3-2.2.7(H). |
| | |
| | ********IMPORTANT INFORMATION******** |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED, PLEASE INCLUDE A |
| | TRANSMITTAL LETTER INDICATING HOW EACH |
| | ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. |
| | NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |