2007-06-08 15:24:54DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SHEET P.1 SANITARY ISOMETRIC RISER DIAGRAM: THE
 FOLLOWING IS REQUIRED AND NEEDS TO BE INDICATED ON THE
 DRAWINGS FOR THE WASHING MACHINE PER FBC-2004
 PLUMBING.
 (A) 406.3 WASTE CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER.
 NOTE: THE WASHING MACHINE BRANCH AND STACK DRAIN ARE
 SIZED WRONG ON THE ISOMETRIC. PLEASE CORRECT ON THE
 RESUBMITTAL.
  
 (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY
 TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS
 FOR RODDING. PLEASE INDICATE THE STANDPIPE ON THE
 RESUBMITTAL.
  
 (C) 708.7 MINIMUM SIZE. CLEANOUTS SHALL
 BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102MM).
 NOTE: CLEANOUT FOR THE WASHING MACHINE SHALL BE THREE
 INCH (3"). PLEASE INDICATE THIS ON THE RESUBMITTAL.
  
 (D) 708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS.
 NOTE: CLEANOUT FOR THE WASHING MACHINE TO BE LOCATED AT
 FOUR FEET ABOVE FINNISH FLOOR (4' A.F.F.). PLEASE
 INDICATE THIS ON THE RESUBMITTAL.
  
 2. SHEET P.1 SANITARY ISOMETRIC RISER DIAGRAM: THE LAV
 IN ROOM 114 IS DRAWN WRONG AND DOES NOT REFLECT THE
 PLUMBING FLOOR PLAN. PLEASE CORRECT ON THE
 RESUBMITTAL.
  
 3. SHEET P.1 SANITARY ISOMETRIC RISER DIAGRAM: THE
 ISOMETRIC DOES NOT REFLECT THE PLUMBING FLOOR PLAN FROM
 THE BUILDING SEWER TO THE MASTER BATH AND ALSO TO THE
 LAVS IN MASTER BATH ROOM #113. PLEASE CORRECT ON THE
 RESUBMITTAL.
  
 4. SHEET P.1 SANITARY ISOMETRIC RISER DIAGRAM AND
 PLUMBING FLOOR PLAN: MASTER BATH ROOM #113 A VENT IS
 REQUIRED FOR THE SHOWER PER TABLE 906.1 A 2" TRAP CAN
 ONLY BE 6' FROM VENT. PLEASE CORRECT ON THE
 RESUBMITTAL.
  
 5. SHEET P.1 SANITARY ISOMETRIC RISER DIAGRAM AND
 PLUMBING FLOOR PLAN: PLEASE SEE RED LINE CORRECTIONS TO
 THE TWO-WAY CLEANOUTS IN THREE PLACES.
  
 6. SHEET P.1 PLUMBING NOTE NUMBER SEVEN (7): PLEASE
 DELETE THE FOLLOWING "FURNISH AND INSTALL APPROVED
 SHOCK ABSORBERS AT EACH PLUMBING FIXTURE GROUP" AND
 PLEASE ADD THE FOLLOWING "PER FBC-2004 PLUMBING,
 SECTION 604.9 A WATER-HAMMER ARRESTOR SHALL BE
 INSTALLED WHERE QUICK-CLOSING VALVES ARE UTILZED AND
 SHALL BE INSTALLED IN ACORDANCE WITH THE MANUFACTURER'S
 SPECIFICATIONS."
  
 7. SHEET P.1 PLUMBING FLOOR PLAN IS INDICATING A GAS
 WATER HEATER AND A GAS STUB W/ SHUTOFF IN THE PROPOSED
 COVERED PATIO AREA. A SEPERATE GAS PERMIT IS REQUIRED
 FOR THIS WORK. PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR THE GAS PERMIT.
  
 A} SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 B} SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
  
 C} TYPE OF GAS, (LP OR NATURAL).
  
 D} BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 E} SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 F} INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 G} SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 H} CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 I} CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  