| 2007-06-26 15:23:18 | BUILDING REVIEW CHECKLIST: |
| | 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY |
| | SEC. 713.13 FLORIDA STATUTE. |
| | |
| | 2- PROVIDE COPY OF IMPACT FEES PAID RECEIPT. |
| | |
| | 3- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE |
| | 9B-72 FOR: |
| | A) GARAGE DOORS THAT MATCH THOSESHOWN ON |
| | ARCHITECTURAL EXTERIOR ELEVATIONS. |
| | |
| | B) METAL ROOF AT NEW CUPOLA. |
| | |
| | C) CUPOLA LOUVERED SCREEN. |
| | |
| | D) WINDOW MULLIONS. |
| | |
| | E) SINGLE HUNG WINDOWS. NOA #02-0123.04 SUBMITTED IS |
| | FOR SMALL MISSILE IMPACT RESISTANT WINDOWS. NEED |
| | PRODUCT APPROVAL FORLARGE MISSILE IMPACT WINDOWS AT |
| | OPENINGS BELOW 30'-0". |
| | |
| | F) ALLSIMPSON STRUCTURAL CONNECTORS SPECIFIED ON |
| | PLANS. |
| | |
| | 4- ARCHITECT NEEDS TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 5- PROVIDE COMPLETE SPECS FOR BBQ GRILLTO BE |
| | INSTALLED IN THE PORCH.SEC. 106.1.2 CITY AMENDMENTS |
| | TO FBC 2004. |
| | |
| | 6- ARCHITECT TO SPECIFY ROOF TILE FASTENING AS REQUIRED |
| | BY SEC. 106.1.1.2 CITY AMENDMENTS TO FBC 2004. ***NOTE: |
| | DON'T SPECIFY PER PRODUCT APPROVAL.PRODUCT APPROVAL |
| | IS ONLY TO VERIFY COMPLIANCE WITH ARCHITECT'S DESIGN |
| | CRITERIA. |
| | |
| | 7- CLARIFYIF LOUVERS AT NEW CUPOLA ARE DECORATIVE OR |
| | FUNCTIONAL. CUPOLA DETAIL SHOWS OPERABLE LOUVERS. SEC. |
| | 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 8- SPECIFY ATTIC VENTILATION AT MAIN ROOF AND CUPOLA. |
| | SEC. R806 OF 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | 9- PROVIDE DRAINAGE PLAN. SEC. R401.3 OF 2004 FLORIDA |
| | RESIDENTIAL CODE.AND, SHOW HOW WATER WILL BE DIVERTED |
| | AWAY FROM NEIGHBOR'S PROPERTY. |
| | |
| | 10- SPECIFY ALL LIVE AND DEAD LOADS, INCLUDING ATTIC |
| | LIVE LOADS AS REQUIRED BY TABLE R301.5 OF 2004 FLORIDA |
| | RESIDENTIAL CODE. |
| | |
| | 11- PROVIDE SOIL TEST REPORT. |
| | |
| | 12- COORDINATE FOOTINGS ON FOUNDATION PLAN WITH FOOTING |
| | SCHEDULE. SIZES DON'T MATCH. |
| | |
| | 13- COORDINATE LINTEL SCHEDULE WITH OPENING SIZES SHOWN |
| | ON PLANS. |
| | |
| | 14- PROVIDE COLUMN SCHEDULE TO VERIFY TYPE OF COLUMNS. |
| | STRUCTURAL PLANS DON'T IDENTIFY THEM. SEC. 106.1.2 CITY |
| | AMENDMENTS TO FBC 2004. |
| | |
| | 15- PROVIDE COMPLETE DETAILS/SPECS/ CONNECTORS AT TOP |
| | AND BOTTOM OF WOOD COLUMNS. SEC. 106.1.2 CITY |
| | AMENDMENTS TO FBC 2004. |
| | |
| | 16- PROVIDE COMPLETE BEAM. SEC. 106.1.2 CITY AMENDMENTS |
| | TO FBC 2004. |
| | |
| | 17- PROVIDE TRUSS ANCHOR SCHEDULE. |
| | ***NOTE: MAKE SURE PROPER CONNECTORS ARE SPECIFIED. EG: |
| | WOOD TO WOOD CONNECTORS, WOOD TO MASONRY CONENCTORS OR |
| | WOOD TO EXISITNG MASONRY WALL CONNECTORS. |
| | AND, SEE CURRENT CATALOG FOR PROPER FASTENER SIZE AND |
| | NUMBER. |
| | |
| | 18- SPECIFY ATTICACCESS SIZE AND LOCATION AT NEW |
| | FAMILY ROOM, GARAGE AND MASTER BEDROOM. SEC. R807 OF |
| | 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | 19- SPECIFY FIREBLOCKING TYPE AND SIZE IN WALL SECTIONS |
| | AS REQUIRED BY SEC. R602.1.2 OF 2004 FLORIDA |
| | RESIDENTIAL CODE. |
| | |
| | 20- PROVIDE COMPLETE DETAIL/ SPECS FORSOFFIT |
| | CONSTRUCTION. SEC. 106.1.2 CITY AMENDMENT TO FBC 2004. |
| | |
| | 21- SPECIFY ROOF PITCH TO VERIFY COMPLIANCE WITH SEC. |
| | R905 OF 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | 22- ROOF FRAMING PLAN DOESN'T SHOW LOCATION OF CUPOLA. |
| | PROVIDE COMPLETE INFORMATION. SEC. 106.1.2 CITY |
| | AMENDMENTS TO FBC 2004. |
| | |
| | 23- OWES $22.52 FOR RADON FEES. |
| | |
| | 24- SHEET A.0: |
| | * THIS IS LEVEL OF ALTERATION 3, NOT 2. REVISE. |
| | ** THIS IS RESIDENTIAL R3, NOT R. REVISE. |
| | *** THIS IS FLOOD ZONE C, NOT '*'. REVISE |
| | |
| | 25- SHEET S.1: |
| | * REVISE NOTE M-4. SEE SEC. R606.4 OF 2004 FLORIDA |
| | RESIDENTIAL CODE. |
| | ** COORDINATE NOTE PS-1 WITH ARCHITECTURAL DRAWINGS. |
| | |
| | NOTE: |
| | PLEASE RETURN REVIEWED SET AFTER CORRECTIONS ARE DONE |
| | TO EXPEDITE THE REVIEW PROCESS. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |