| 2007-09-18 12:59:08 | BUILDING PLAN REVIEW |
| | PERMIT: 07050617 |
| | ADD: 5405 BROADWAY |
| | CONT: RAY GRAEVE & SONS CONST LLC |
| | TEL: (561)432-5690 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW 2ND |
| | ACTION: DENIED |
| | |
| | 1) --- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | 2) F.S. 481.221 (2) ALL FINAL CONSTRUCTION DOCUMENTS |
| | AND INSTRUMENTS OF SERVICE WHICH INCLUDE DRAWINGS, |
| | PLANS SPECIFICATIONS, OR REPORTS PREPARED OR ISSUED BY |
| | THE REGISTERED ARCHITECT AND BEING FILED FOR PUBLIC |
| | RECORD SHALL BEAR THE SIGNATURE AND SEAL OF THE |
| | REGISTERED ARCHITECT WHO PREPARED OR APPROVED THE |
| | DOCUMENT AND THE DATE ON WHICH THEY WERE SEALED. NOTE: |
| | ONE OF THE SHEET IS NOT SIGN OR DATED. |
| | |
| | 3) THE PRODUCT APPROVALS SUBMITTED ARE MISSING THE |
| | INSTALLATION REPORTS. WHEN RE-SUBMITTING, MATCH THE FL# |
| | WITH THE CORRECT INSTALLATION REPORT. PROVIDE THE |
| | PRODUCT APPROVAL FOR THE GLASS BLOCK AND NEW PRECAST |
| | LINTEL, ALSO INDICATE THE SIZE OF THE LINTIL. IS IT |
| | 4",6",8" OR 12". FBC 2104.1.5 THE MINIMUM LENGTH OF END |
| | SUPPORT FOR LINTELS SHALL BE 4". INDICATE THE OPENING |
| | DIMENTION. |
| | |
| | 4) FBC 106.1.1 CONSTRUCTION DOCUMENTS SHALL BE OF |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS. PROVIDE A WALL LEGEND INDICATING WHICH |
| | WALLS ARE NEW AND WHICH ONES ARE EXISTING. IN THE |
| | LEGEND SHOW A DETAIL OF EACH TYPE OF WALL. |
| | |
| | 5) 110.2* W. P. B. ADMINISTRATIVE |
| | CODE, INFORMATION THAT IS REQUIRED FOR |
| | RECORD KEEPING & FOR CERTIFICATE OF |
| | OCCUPANCY: |
| | A) THE EDITION OFTHE CODE UNDER WHICH |
| | THE PROJECT WAS DESIGNED. |
| | B) THE USE AND OCCUPANCY, IN ACCORDANCE |
| | WITH THE PROVISIONS OF CHAPTER 3. |
| | C) THE TYPE OF CONSTRUCTION AS DEFINED |
| | IN CHAPTER 6, TABLE 601. |
| | D) THE DESIGN OCCUPANT LOAD, SEE 1004. |
| | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS |
| | PROVIDED, WHETHER THE SPRINKLER SYSTEM |
| | IS REQUIRED. |
| | ) NUMBER OF FLOORS |
| | ) NUMBER OF ROOMS |
| | ) SQ. FT. FOOTPRINT |
| | ) SQ. FT. UNDER ROOF (TOTAL) |
| | ) OCCUPANT LOAD |
| | |
| | 6) STATE THE LEVEL OF ALTERATION IN ACCORDANCE WITH |
| | CH.3 OF THE 2004 EXISTING FBC. ARE THE INTERIOR WALLS |
| | CONCRETE BLOCK? |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | 805-6726 |