| Date |
Text |
| 2007-06-11 17:19:04 | ******DENIED***** |
| | |
| | |
| | 1.THE SUBMITTED PLANS DO NOT INDICATE WHAT THE |
| | MODIFICATIONS TO THE EXISTING STRUCTURE ARE TO BE |
| | CONDUCTED. |
| | |
| | 2.THE 2003 EDITION OF NFPA 101 AND THE 2004 EDITION |
| | OF THE FLORIDA FIRE PREVENTION CODE SHALL BE |
| | REFERENCED. |
| | |
| | 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 4.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL |
| | BE REMOVED FROM THE THE SITE AT THE END OF EACH SHIFT |
| | OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. |
| | |
| | 5.ON THE APPROPIATE EXTERIOR ELEVATION WHICH FRONTS |
| | BROADWAY AVENUE, DISPLAY/SHOW THE NUMERICAL ADDRESS. AS |
| | PER WEST PALM BEACH CODE, THOSE NUMBERS SHALL BE NO |
| | LESS THAN 6" IN HEIGHT AND NO LESS THAN 1" IN WIDTH. |
| | |
| | 6.IF THE BUILDING OR PORTION OF THE BUILDING IS TO BE |
| | OCCUPIED DURING THE SCOPE OF WORK, REQUIRED MEANS OF |
| | EGRESS AND REQUIRED FIRE PROTECTION FEATURES SHALL BE |
| | OPERATIONAL AND MAINTAINED. |
| | |
| | 7.BASED UPON THE ASSUMPTION THAT THIS STRUCTURE IS AN |
| | EXISTING BUSINESS OCCUPANCY, THE INTERIOR WALL AND |
| | CEILING MATERIALS SHALL BE CLASS A OR CLASS B IN EXITS |
| | AND EXIT ACCESS CORRIDORS, AND SHALL BE CLASS A, CLASS |
| | B, OR CLASS C IN ALL OTHER AREAS.BE SPECIFIC |
| | |
| | 8.PROVIDE LOCATION OF THE 2A:10BC RATED FIRE |
| | EXTINGUISHER(S) SATISFYING THE 75' TRAVEL DISTANCE. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED |
| | |
| | |
| | CAPT. MICHEAL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |