| Plan Review Notes For Permit 07050608 |
| Permit Number |
07050608 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-07-25 09:27:01 | *** DENIED *** | | | 1) BUILDING PLANS PAGE A-1 SHOWS THE NEW ADDITION IS | | | 638 FEET UNDER AIR, THEREFOR THE ENERGY CALCULATIONS | | | CAN NOT BE DONE ON FORM 600C-04R, SEE 2004 FBC | | | 13-600.3.C PLEASE CORRECT. | | | | | | 2) BUILDING PLANS PAGES A-1 AND D-1 ARE SHOWING THE | | | WRONG R VALUE FOR THE ATTIC AND WALL INSULATION, SEE | | | ENERGY CALCULATIONS PLEASE CORRECT. | | | | | | 3) PLEASE SHOW THE BATHROOM EXHAUST FANS AND THE | | | CLOTHES DRYER VENT ON THE MECHANICAL PLANS ALSO. | | | | | | 4) PLEASE SHOW THE CORRECT JOB ADDRESS ON THE | | | MECHANICAL PLANS, SEE 2004 FBC CITY WPB AMEND. | | | 106.1.3. | | | | | | 5) ALL INFORMATION, DRAWINGS, (MECHANICAL PLANS) | | | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE | | | PRINTED NAME AND SIGNATURE OF THE PERSON RESPONSIBLE | | | FOR THE DESIGN. PER FBC 104.2.1 . | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|