| Plan Review Notes For Permit 07050608 |
| Permit Number |
07050608 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-07-25 07:43:22 | | | | | | | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | 1} PROVIDE LOAD CALCULATIONS PER ARTICLE 220 PART III, | | | STANDARD OR PART IV OPTIONAL, INDICATE METHOD USED. | | | THIS COMMENT WAS INTENDED TO GET A LOAD CALCULATION FOR | | | THE ENTIRE SERVICE, NOT FOR INDIVIDUAL PANELS, WHICH | | | MAY OR MAY NOT BE ABLE TO BE LOADED TO THEIR MAXIMUM | | | OCP, DEPENDING ON HOW THE LOAD IS BALANCED. | | | | | | 2} THE EXISTING ELECTRICAL PANEL NOTES ON SHEET E-1, | | | INCORRECTLY INDICATE THE ELECTRICAL PLAN AND LEGEND ON | | | SHEET A-3. | | | | | | 3} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE | | | PER 210.11(C) (3), INCLUDE IN THE SCHEDULE THIS WAS NOT | | | ON THE SCHEDULE IN THE RESUBMITTAL.. | | | | | | 4} THE DESIGNER WILL VERIFY THAT THE AIR CONDITIONING | | | LOAD WILL OR WILL NOT INCREASE AS THERE IS A MECHANICAL | | | PERMIT APPLICATION FOR THIS PROJECT. ADD THE | | | APPROPRIATE LOADS TO THE SERVICE CALCULATIONS AND | | | LOCATE THE UNITS ON THE PLAN.SEE M1305.1.3.1 RES FBC, | | | 210.63, 210.70 NEC. | | | | | | 5} THE STACK WASHER AND DRYER SHOWN IN THE ADDITION, | | | ARE NOT ON THE PANEL SCHEDULE. THERE IS NO WASHER AND | | | DRYER ON THE PANEL SCHEDULE. | | | | | | 6} CIRCUIT #18, PANEL A, 30 AMP OCP,#12 WIRE,IS A | | | VIOLATION OF 310.16. | | | | | | 7} THE A/C LOAD IS UNCLEAR, CLARIFY "AC#1 & #2 COMP", | | | CIRCUITS 9,11,13,15. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|