2007-07-25 07:43:22 
  
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} PROVIDE LOAD CALCULATIONS PER ARTICLE 220 PART III,
 STANDARD OR PART IV OPTIONAL, INDICATE METHOD USED.
 THIS COMMENT WAS INTENDED TO GET A LOAD CALCULATION FOR
 THE ENTIRE SERVICE, NOT FOR INDIVIDUAL PANELS, WHICH
 MAY OR MAY NOT BE ABLE TO BE LOADED TO THEIR MAXIMUM
 OCP, DEPENDING ON HOW THE LOAD IS BALANCED.
  
 2} THE EXISTING ELECTRICAL PANEL NOTES ON SHEET E-1,
 INCORRECTLY INDICATE THE ELECTRICAL PLAN AND LEGEND ON
 SHEET A-3.
  
 3} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE
 PER 210.11(C) (3), INCLUDE IN THE SCHEDULE THIS WAS NOT
 ON THE SCHEDULE IN THE RESUBMITTAL..
  
 4} THE DESIGNER WILL VERIFY THAT THE AIR CONDITIONING
 LOAD WILL OR WILL NOT INCREASE AS THERE IS A MECHANICAL
 PERMIT APPLICATION FOR THIS PROJECT. ADD THE
 APPROPRIATE LOADS TO THE SERVICE CALCULATIONS AND
 LOCATE THE UNITS ON THE PLAN.SEE M1305.1.3.1 RES FBC,
 210.63, 210.70 NEC.
  
 5} THE STACK WASHER AND DRYER SHOWN IN THE ADDITION,
 ARE NOT ON THE PANEL SCHEDULE. THERE IS NO WASHER AND
 DRYER ON THE PANEL SCHEDULE.
  
 6} CIRCUIT #18, PANEL A, 30 AMP OCP,#12 WIRE,IS A
 VIOLATION OF 310.16.
  
 7} THE A/C LOAD IS UNCLEAR, CLARIFY "AC#1 & #2 COMP",
 CIRCUITS 9,11,13,15.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718