Plan Review Notes
Plan Review Notes For Permit 07050608
Permit Number 07050608
Review Stop E
Sequence Number 1
Notes
Date Text
2007-05-31 12:32:29 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} PROVIDE A LOAD CALCULATION PER 220.31, INCLUDE ADDED
 LOADS. REQUIRED BY 215.5NEC
  
 2} PROVIDE A PANEL SCHEDULE PER 408.4. PLEASE SEE NEW
 VERBAGE FOR 2005 NEC: "THE IDENTIFICATION SHALL INCLUDE
 SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE
 DISTINGUISHED FROM ALL OTHERS."
  
 3} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE
 PER 210.11(C) (3), INCLUDE IN THE SCHEDULE.
  
 4} R313.1.1 SMOKE ALARMS SHALL BE LOCATED AS REQUIRED
 IN NEW DWELLINGS WHEN REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR. SEE ARTICLE FOR COMPLETE TEXT. NOTE # 14
 INDICATES "BEDROOM ADDITIONS", WHICH IS CORRECT. BUT
 NOTE FOR FUTURE PROJECTS THE TEXT IN THE RESIDENTIAL
 CODE INDICATES ANYTIME A PERMIT IS PULLED FOR ANY
 INTERIOR WORK, THE EXISTING BEDROOMS MUST COMPLY.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]