Plan Review Notes
Plan Review Notes For Permit 07050608
Permit Number 07050608
Review Stop B
Sequence Number 1
Notes
Date Text
2007-06-30 11:15:52 
  
 DENIED
  
 1)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH
 COUNTY. THE ACTUAL PERMIT
 SETS OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. THE STAMP IS
 REQUIRED ALTHOUGH FEES MAY NOT BE
 PLEASE CALL (561) 233-5025 FOR MORE
 INFORMATION.
  
 2)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON
 SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER
 ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE
 ADDED TO THE PERMIT APPLICATION FEES. TOTAL AMOUNT DUE
 $ 6.50
  
 3)PLANS AND SPECIFICATIONS SHALL COMPLY WITH THE 2004
 FL BLDG CODE WITH 2006 AMENDMENTS
  
 4)THE 2006 AMENDMENTS TO THE 2004 FBC REQUIRE
 BUILDINGS LOCATED WITHIN EXP B TYPE TERRAIN THAT IS
 DIRECTLY ADJACENT TO EXP C TYPE TERRAIN SUCH AS OPEN
 GOLF COURSES AND BODIES OF WATER FOR A DISTANCE OF 600
 FEET OR MORE IN ANY QUADRANT TO BE IN AN EXP C
 CATEGORY. PLEASE ADJUST THE DESIGN PARAMETERS AND WIND
 PRESSURES ACCORDINGLY
  
 5)PROVIDE EXISTING AND NEW AREA SQUARE FOOTAGE ON THE
 DRAWINGS
  
 6)PROVIDE EXISTING FLOOR PLAN WITH DETAILS ON ANY
 DEMOLITION OR REWORKING OF LAYOUT
  
 7)PROVIDE SITE PLAN 2 COPIES OF A RECENT SURVEY
 SHOWING THE PROPOSED BUILDING/ADDITION WITH ALL SIDE
 AND REAR SETBACKS
  
 8)PROVIDE ATTIC ACCESS ON DRAWINGS TO ALL AREAS AS
 REQUIRED PER R807.1 FBC RES.
  
 9)SUBMIT ENGINEERED TRUSS DRAWINGS FOR THE FLOOR AND
 ROOF TRUSSES THAT
 COMPLY WITH R802.10.1 FBC WITH PERMIT
 APPLICATION OR BEFORE INSTALLATION THAT
 HAVE BEEN REVIEWED AND APPROVED BY THE
 DESIGNER OF RECORD
  
 10)SUBMIT ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND
 DATED BY PREPARER AND OWNER/AGENT PRIOR
 TO SUBMITTAL
  
 11)PROVIDE ATTACHMENT METHOD FOR FLOOR TRUSSES TO NEW
 GIRDER TRUSS
  
 12)CLARIFY ATTACHMENT OF NEW FRAMED WALLS TO EXISTING
 TIE BEAM IS THE SIMPSON HTT22 ON EVERY STUD OR JUST THE
 CORNERS, IF THE LATTER WHAT CONNECTORS ARE TYING THE
 WALLS TO TIE BEAM
  
 13)DRAWING STATES THEIR ARE 2 CASEMENT WINDOWS 36 X
 72 BUT PRODUCT APPROVAL DOES NOT ALLOW FOR THAT SIZE.
 MAX HEIGHT FOR 36" WIDTH IS 63" ALSO NOTE THE GLASS
 TYPE AS THE "A" TYPE WILL NOT MEET THE DESIGN PRESSURES
 REQUIRED. IF 2 SEPARATE WINDOWS ARE USED A PRODUCT
 APPROVAL FOR MULLIONS IS REQUIRED BUT CASEMENT PRODUCT
 APPROVAL HAS A "XX" CONFIGURATION WITH BUILT IN MEETING
 RAIL
  
 14)THE PRODUCT APPROVAL FOR ROOF TILES DOES NOT HAVE
 STATE APPROVAL THE STATUS IS (APPLIED FOR) AND THE
 COMPLIANCE REPORT WILL BE THE MIAMI-DADE NOA NOT THE
 COMPLETE INSTALLATION GUIDE THAT WAS SUBMITTED. PLEASE
 REMOVE THIS FROM PACKAGE AND SUBMIT THE MIAMI-DADE NOA
 FOR THE TYPE OF ROOF TILE THAT WILL BE USED AND A LOCAL
 PRODUCT APPROVAL WILL BE GRANTED BASED ON THAT NOA.
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  