Plan Review Notes
Plan Review Notes For Permit 07050562
Permit Number 07050562
Review Stop B
Sequence Number 3
Notes
Date Text
2008-03-19 17:05:27RESIDENTIAL ADDITION, BUILDING REVIEW THIRD CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
 ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK
 UP.
  
 2- MISSING3 SHEETS THAT WERE SUBMITTED ON PREVIOUS
 SUBMITTALS.MISSINGSHEETS 1 OF 6, 5 OF 6 AND 6 OF
 6.
  
 3- BRING ALL DRAWINGS FORTHE HISTORICAPPROVAL
 STAMP PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 4- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) SWING DOOR FOR STORAGE ROOM.PRODUCT APPROVAL
 SUBMITTED IS MISSING THE TECHNICAL DRAWINGS.
 B) AWNING WINDOWS. PRODUCT APPROVAL SUBMITTED IS
 MISSING THE TECHNICAL DRAWINGS.
 C)ALL USP AND SIMPSON STRUCTURAL CONNECTORS.
 PRODUCT APPROVALS SUBMITTED ARE MISSING THE PAGE WHERE
 SPECIFIED CONNECTORS ARE SHOWN.
  
 5- ENGINEER OF RECORD TO REVISE LETTER LISTING REVIEWED
 PRODUCT APPROVALS. PRODUCT APPROVAL NUMBER FOR USP
 CONNECTORS AND SIMPSON CONNECTORS ARE REVERSED.
  
 6- PROVIDE THE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 13-600FBC 2004.(REPEAT COMMENT, NOT ADDRESSED AT
 ALL). PLEASE, MAKE SURE CORRECT REVISED FORM IS USED TO
 AVOID UNNECESSARY DELAYS.
  
 7- CONTRACTOR TO UPDATE COUNTY REGISTRATION WITH PERMIT
 CLERK.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712