| 2007-10-04 14:55:20 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | | NONCOMPLIANT WITH THE FOLLOWING: | | | | | | THESE COMMENTS WERE ON THE PREVIOUS REVIEW AND MUST BE | | | ADDRESSED WHEN INSTALLING OR RELOCATING A SERVICE: | | | | | | 4} PROVIDE A RISER DIAGRAM WITH CONDUCTOR AND CONDUIT | | | SIZE AND TYPE, GROUNDING DETAILS, SERVICE EQUIPMENT AND | | | PANEL LOCATIONS PER 106.3.5.4 FBC.SEE 250.52(A)(3) | | | FOR FOOTER STEEL. | | | | | | 5} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT | | | CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE | | | EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT | | | IS EQUAL TO OR GREATER THAN THE AVAILABLE FAULT. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|