2007-10-12 11:28:17RESIDENTIAL ADDITIONBUILDING REVIEW SECOND
 CHECKLIST.
 REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE, EXISTING
 BUILDING 2004 AND FBC 2004.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE. REPEAT COMMENT.
  
 2- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD
 (561)233-5115)TO VERIFY IF IMPACT FEES ARE DUE. BRING
 BACK STAMPED PLANS AND COPY OF PAID RECEIPT IF IMPACT
 FEES ARE DUE. REPEAT COMMENT.
  
 3- HOUSE IS LOCATED IN THE HISTORIC DISTRICT. NEED TO
 BRING REVISED PLANS TO THE FIFTH FLOOR OF CITY HALL TO
 GET PLANS APPROVED AND STAMPED BY THE HISTORIC
 DEPARTMENT PRIOR TO SUBMITTAL TO THIS OFFICE.***NOTE:
 THIS COMMENT WAS NOT ADDRESSED ON PREVIOUS CHECKLIST
 BECAUSE ONLY ON 8/30/07 WAS THIS PROPERTY POSTED AS
 BEING IN THE HISTORIC DISTRICT.
  
 4- PROVIDE 2 COPIES OF PRODUCT APPROVALSAS REQUIRED
 BY DCA RULE 9B-72 FOR (REPEAT COMMENT):
 A) FLAT ROOF ASSEMBLY.AND, CLEARLY IDENTIFY
 SPECIFIC ASSEMBLY TO BE INSTALLED ALONG WITH SPECIFIC
 FASTENING OPTION AND RAS 117 CALCULATIONS FOR NAIL
 ENHANCING AT PERIMETER AND CORNER AREAS AS REQUIRED BY
 GENERAL LIMITATION #7.IF GENERAL LIMITATION #7
 REQUIRES CALCULATIONS TO BE DONE BY ANY OF THE
 PROFESSIONALS LISTED IN THE GENERAL LIMITATION, THEN
 SUCH INFORMATION SHALL BE PROVIDED. SEE ATTACHED COPY
 OF CITY POLICY FOR ROOFING PERMITS.
  
 B) SWING DOOR FOR STORAGE ROOM.
  
 C) AWNING WINDOWS.
  
 D) STORM SHUTTERS. AND, PROVIDE COMPLETE
 INSTALLATION SCHEDULE.SEC. 106.1.2 CITY AMENDMENTS TO
 FBC 2004.SEE ATTACHED SAMPLE. AND, MARK ON DRAWINGS
 SPECIFIC MOUNTING CONDITIONSAND ANCHOR TYPE AND
 SPACING TO BE USED.
  
 E) ALL SIMPSON AND USP CONNECTORS SPECIFIED ON
 PLANS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL COVER
 PAGE AND THE PAGE WHERE SELECTED CONNECTOR IS SHOWN.
  
 5- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
 ***NOTE: ENGINEER PROVIDED SEPARATE SHEET LISTING ALL
 THE PRODUCT APPROVALS HE APPROVED FOR THIS PROJECT BUT
 MOST OF THEPRODUCT APPROVALS LISTED IN THE LETTER
 DON'T CORRESPOND TO THOSESHOWN ON PLANS.EG:
 ENGINEERAPPROVEDSHINGLES,WHILE PLANS SHOW FLAT
 ROOF.ENGINEER APPROVED GARAGE DOOR, WHILE THERE IS
 NOT GARAGE DOOR BUT STORAGE DOOR. ENGINEER APPROVED
 SINGLE HUNG WINDOWS, WHILE PLANS SHOW AWNING WINDOWS.
 ENGINEER TO CAREFULLY REVIEW PLANS AND PRODUCT
 APPROVALS AND PROVIDE CORRECT LIST OR PROVIDE PRODUCT
 APPROVAL REVIEW STAMP ON EACH PRODUCT APPROVAL.
  
 6- PROVIDE THE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 13-600 FBC 2004. PLEASE MAKE SURE REVISED 2004 FORM
 IS USED. REPEAT COMMENT.
  
 7- OWES $1117.48FOR UPDATED VALUATIONAS REQUIRED BY
 SEC. 108.3 CITY AMENDMENTS TO FBC 2004.
 VALUE WAS REVISED FROM PREVIOUS CHECKLIST BECAUSE FLOOR
 AREAS WERE REVISED ON PLANS.
  
 8- SHEET S-1:
 A) REVISE FLOOR TO FLOOR CONNECTION DETAIL:
 * IS 2" O.C. THE CORRECT SPACING OF REBARS?.REPEAT
 COMMENT.
 ***NOTE:SPECIFICATIONS FOR THIS DETAIL MAKE NO SENSE.
 PLEASE RE-WRITEAS REQUIRED TO CLARIFY.
  
 B) F1 DETAIL:KEY ON PLANS WHERE IS THIS DETAIL
 TAKEN AT. THIS DETAIL DOESN'TCORRESPOND TO THE NEW
 ADDITION. REVISE AS REQUIRED. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 C) FOUNDATION PLAN AND FLOOR PLAN SHOWS NO RECESS AT
 DOORS THRESHOLDS.DRAW CORRECTLY AND SPECIFY THE
 DROPS. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. REPEAT
 COMMENT.
  
 E) IF PATIO SLAB IS EXISTING, THEN PROVIDE COMPLETE
 DETAILS/SPECIFICATIONS SHOWING HOW FORMINGTHE NEW
 CONCRETE PAD UNDER THE SLAB FOR STEEL COLUMNS. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 9- SHEET S-2:
 A) UPDATE TRUSS ANCHOR SCHEDULE. SEE CURRENT CATALOG
 AND REVISE AS REQUIRED.OTHERWISE, PROVIDE COMPLETE
 ENGINEERING ANALYSIS FOR SIZE, NUMBER AND UPLIFT LOADS
 THAT DIFFER FROM THOSE TESTED AND PUBLISHED BY THE
 MANUFACTURER. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
 REPEAT COMMENT.
  
 B) REVISE ROOF SHEATHING NAIL TYPE. SEEREVISED
 SEC. R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL CODE FOR
 MINIMUM TYPE OF NAILAND REVISE AS REQUIRED. REPEAT
 COMMENT.
  
 C)CONNECTORS SPECIFIED ON ROOF FRAMING PLAN ARE
 NOT APPROPRIATE ACCORDING TO THE STRUCTURE TO BE
 ATTACHED TO.NEED TO SPECIFYWOOD TO MASONRY
 CONNECTORS AT EXISTING WALL AND WOOD TO WOOD CONNECTORS
 AT NEW WOOD BEAM.REVISE AS REQUIRED. SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004. REPEAT COMMENT.
  
 D) SPECIFY CONNECTORS AT TOP AND BOTTOM OF STEEL
 COLUMNS. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. NEED
 TO SPECIFY TOP CONNECTOR AT CORNER AREA. SEE ROOF
 FRAMING PLAN.
  
 10- SHEET D-1:
 A) TYPICALWALL SECTION DOESN'T CORRESPOND TO
 PROPOSED FLOOR PLAN AND ROOF FRAMING PLAN. REVISE AS
 REQUIRED. REPEAT COMMENT.REVISE SIZE OF ROOF
 RAFTERS.
  
  
 B) PROVIDE COMPLETE SPECIFICATIONS FOR CONCRETE CURB
 SHOWN ON TYPICAL WALL SECTION. SPECIFY HOW LONGIS THE
 5/8" DIAM. THREADUSED TO CONNECT THE WALL 2X6 WOOD
 PLATE TO THE FOOTING. SEC. 106.1.2 CITY AMENDMENTS TO
 FBC 2004.
  
 C) TYPICAL WALL SECTION: SPECIFY HOW ARE 2X6WOOD
 STUDS FASTENED TO THE BOTTOM PLATE. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 11- PLEASE PROVIDE WRITTEN RESPONSE TO THIS CHECKLIST
 TOMAKE SURE ALL ITEMS ARE ADDRESSED AND TO EXPEDITE
 THE REVIEW PROCESS.
  
  
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712