| Plan Review Notes For Permit 07050562 |
| Permit Number |
07050562 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-05-31 11:43:01 | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | 1} TWO SETS OF ALL DOCUMENTS MUST BE SUBMITTED FOR | | | REVIEW PER 106.1 FBC AS AMENDED. | | | | | | 2} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC. | | | IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417 | | | FS, RESPECTIVELY. | | | | | | 3} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE | | | PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI | | | PROTECTED PER 210.8(A) (1). THE PARTIAL PANEL SCHEDULE | | | DOES NOT INDICATE THIS. | | | | | | 4} PROVIDE A RISER DIAGRAM WITH CONDUCTOR AND CONDUIT | | | SIZE AND TYPE, GROUNDING DETAILS, SERVICE EQUIPMENT AND | | | PANEL LOCATIONS PER 106.3.5.4 FBC.SEE 250.52(A)(3) | | | FOR FOOTER STEEL. | | | | | | 5} PER 110.9 AND 110.10: OBTAIN THE | | | AVAILABLE FAULT CURRENT AT THE UTILITY | | | AND CALCULATE THE SAME AT THE EQUIPMENT. | | | INDICATE THE AIC RATING FOR THE | | | EQUIPMENT IS EQUAL TO OR GREATER THAN | | | THE AVAILABLE FAULT. | | | | | | 6} R313.1.1 SMOKE ALARMS SHALL BE LOCATED AS REQUIRED | | | IN NEW DWELLINGS WHEN REPAIRS OR ADDITIONS REQUIRING A | | | PERMIT OCCUR. SEE ARTICLE FOR COMPLETE TEXT. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|