| Date |
Text |
| 2007-06-25 16:34:10 | BUILDING REVIEW CHECKLIST: |
| | 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY |
| | SEC. 713.13 FLORIDA STATUTE. |
| | |
| | 2- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD |
| | (561)233-5115)TO VERIFY IF IMPACT FEES ARE DUE. BRING |
| | BACK STAMPED PLANS AND COPY OF PAID RECEIPT IF IMPACT |
| | FEES ARE DUE. |
| | |
| | 3- NEED TO PROVIDE 2 COMPLETE SETS OF DRAWINGS. ONLY |
| | ONE WAS SUBMITTED. |
| | |
| | 4- PLANS NEED TO HAVE ENGINEER'S SEAL AND ORIGINAL |
| | SIGNATURE AS REQUIRED BY CHAPTER 471 FLORIDA STATUTE. |
| | |
| | 5- PROVIDE 2 COPIES OF PRODUCT APPROVALSAS REQUIRED |
| | BY DCA RULE 9B-72 FOR: |
| | A) FLAT ROOF ASSEMBLY.AND, CLEARLY IDENTIFY |
| | SPECIFIC ASSEMBLY TO BE INSTALLED ALONG WITH SPECIFIC |
| | FASTENING OPTION AND RAS 117 CALCULATIONS FOR NAIL |
| | ENHANCING AT PERIMETER AND CORNER AREAS AS REQUIRED BY |
| | GENERAL LIMITATION #7.IF GENERAL LIMITATION #7 |
| | REQUIRES CALCULATIONS TO BE DONE BY ANY OF THE |
| | PROFESSIONALS LISTED IN THE GENERAL LIMITATION, THEN |
| | SUCH INFORMATION SHALL BE PROVIDED. SEE ATTACHED COPY |
| | OF CITY POLICY FOR ROOFING PERMITS. |
| | |
| | B) SWING DOOR FOR STORAGE ROOM. |
| | |
| | C) AWNING WINDOWS. |
| | |
| | D) STORM SHUTTERS. AND, PROVIDE COMPLETE |
| | INSTALLATION SCHEDULE.SEC. 106.1.2 CITY AMENDMENTS TO |
| | FBC 2004.SEE ATTACHED SAMPLE. AND, MARK ON DRAWINGS |
| | SPECIFIC MOUNTING CONDITIONSAND ANCHOR TYPE AND |
| | SPACING TO BE USED. |
| | |
| | E) ALL SIMPSON AND USP CONNECTORS SPECIFIED ON |
| | PLANS. |
| | |
| | 6- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 7- PROVIDE THE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| | 13-600 FBC 2004. PLEASE MAKE SURE REVISED 2004 FORM |
| | IS USED. |
| | |
| | 8- OWES $105.62 FOR UPDATED VALUATIONAS REQUIRED BY |
| | SEC. 108.3 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 9- SQUARE FOOTAGE TABULATIONS ON SHEET A-1 ARE |
| | INCORRECT. REVISE AS REQUIRED. |
| | |
| | 10- SHEET S-1: |
| | A) REVISE FLOOR TO FLOOR CONNECTION DETAIL: |
| | * IS 2" O.C. THE CORRECT SPACING OF REBARS? |
| | |
| | **WHAT'S "EPCON"? |
| | |
| | B) F1 DETAIL: |
| | * SHOW GRADE TO VERIFY COMPLIANCE WITH SEC. R403.1.4 |
| | OF 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | C) PROVIDE COMPLETE SPECS FOR SIZE OF STEEL COLUMNS |
| | AT"PATIO" AREA.SPECIFY STEEL THICKNESS. SEC. |
| | 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | |
| | D) FOUNDATION PLAN AND FLOOR PLAN SHOWS NO RECESS AT |
| | DOORS THRESHOLDS.DRAW CORRECTLY AND SPECIFY THE |
| | DROPS. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | |
| | E) PROVIDE COMPLETE SPECS AT PATIO SLAB. EG: SLAB |
| | THICKNESS AND EDGE REINFORCEMENT. SEC. 106.1.2 CITY |
| | AMENDMENTS TO FBC 2004. |
| | |
| | 11- SHEET S-2: |
| | A) UPDATE TRUSS ANCHOR SCHEDULE. SEE CURRENT CATALOG |
| | AND REVISE AS REQUIRED.OTHERWISE, PROVIDE COMPLETE |
| | ENGINEERING ANALYSIS FOR SIZE, NUMBER AND UPLIFT LOADS |
| | THAT DIFFER FROM THOSE TESTED AND PUBLISHED BY THE |
| | MANUFACTURER. SEC. 106.1.2 CITY AMENDMENTS TO FBC |
| | 2004. |
| | |
| | B) REVISE ROOF SHEATHING NAIL TYPE. SEEREVISED |
| | SEC. R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL CODE FOR |
| | MINIMUM TYPE OF NAILAND REVISE AS REQUIRED. |
| | |
| | C)CONNECTORS SPECIFIED ON ROOF FRAMING PLAN ARE |
| | NOT APPROPRIATE ACCORDING TO THE STRUCTURE TO BE |
| | ATTACHED TO.NEED TO SPECIFYWOOD TO MASONRY |
| | CONNECTORS AT EXISTING WALL AND WOOD TO WOOD CONNECTORS |
| | AT NEW WOOD BEAM.REVISE AS REQUIRED. SEC. 106.1.2 |
| | CITY AMENDMENTS TO FBC 2004. |
| | |
| | D) SPECIFY CONNECTORS AT TOP AND BOTTOM OF STEEL |
| | COLUMNS. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 12- SHEET D-1: |
| | A) TYPICALWALL SECTION DOESN'T CORRESPOND TO |
| | PROPOSED FLOOR PLAN AND ROOF FRAMING PLAN. REVISE AS |
| | REQUIRED. |
| | ***ALSO, COORDINATE TYPICAL WALL SECTION WITH FRAMNG |
| | DETAIL/SECTIONS FOR DOOR AND WINDOW OPENINGS. SEC. |
| | 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | |
| | B) FRAMING DETAIL AT DOOR OPENING DOESN'T SHOW ANY |
| | HEADER. REVISE AS REQUIRED. SEC. 106.1.2 CITY |
| | AMENDMENTS SOT FBC 2004. |
| | |
| | C) REVISE DESIGN DATA NOTE H. SEE 2004 FLORIDA |
| | RESIDENTIAL CODE FOR CORRECT CODE TO BE USED AND REVISE |
| | AS REQUIRED. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |