Plan Review Notes
Plan Review Notes For Permit 07050534
Permit Number 07050534
Review Stop M
Sequence Number 2
Notes
Date Text
2007-08-29 16:06:53PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (WPB), FLORIDA
 ADMINISTRATIVE CODE (FAC), AND FLORIDA STATUTES (FS).
  
 *** DENIED ***
 1) THE ENGINEER WHO'S INFORMATION IS IN THE TITLE BLOCK
 MUST SIGN AND SEAL THE PLANS. SEE FAC 61G15-23.002
 SEAL, SIGNATURE AND DATE SHALL BE AFFIXED.
  
 2) MECHANICAL PLAN PAGE 9 NEEDS TO SHOW THE BATHROOM
 EXHAUST FAN AND CFM'S, IF ONE IS TO BE INSTALLED AS
 SHOWN ON ELECTRICAL PLAN PAGE 7. SEE 2004 FBC/RES.
 R303.3.
  
 3) ENERGY CALCULATIONS SHOW A 12,000 BTU 13 SEER A/C
 SYSTEM IS TO BE INSTALLED, MECHANICAL PLANS SHOW NO A/C
 SYSTEM TO BE INSTALLED. PLEASE CORRECT ENERGY CAL'S. TO
 SHOW NEW WORK FOR ADDITION OR WHOLE HOUSE NEW AND
 EXISTING, SEE 13-101.2.2. IT MAY BE EASIER TO SUBMIT
 FORM 600C-04 FOR THE ADDITION ONLY.
  
 4) ENERGY CAL'S. LINE 10A SHOW ATTIC INSULATION TO BE
 R-30, PLANS PAGE 2 SHOWS THE ATTIC INSULATION TO BE
 R-19. THE TWO MUST COINCIDE, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]