2007-05-23 16:38:29*** DENIED ***
 1) INFORMATION MISSING FROM TITLE BLOCK. ENGINEER'S
 LICENSE NUMBER 37549. NUMBER 27186 IS SHOWING AS THE
 LICENSE NUMBER BUT THAT IS THE CERTIFICATE OF
 AUTHORIZATION NUMBER, PLEASE CORRECT. SEE FAC
 61G15-23.002 (2)A TITLE BLOCK ON EACH SHEET
 CONTAINING THE PRINTED NAME, ADDRESS, AND LICENSE
 NUMBER OF THE ENGINEER OR IF APPLICABLE, THE NAME AND
 LICENSE NUMBER OF THE ENGINEER, AND THE NAME, ADDRESS
 AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS WILL SATISFY THIS REQUIREMENT.
  
 2) PLEASE SUBMIT ENERGY CALCULATIONS, SEE 2004 FBC
 13-101.2.2. AND PLEASE HAVE ENERGY CAL'S. SIGNED BY
 OWNER/AGENT ALSO, SEE 2004 FBC 13-600.3.ABC.2.
  
 3) PLEASE PROVIDE FOR RETURN AIR FOR THE BEDROOM, SEE
 2004 FBC/R M1602.4.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.