| 2007-06-26 16:38:45 | |
| | |
| | DENIED |
| | |
| | 1)ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME, |
| | ADDRESS, AND LICENSE NUMBER ON EACH SHEET THAT BEARS |
| | THEIR SEAL PER 61G15-23.002(2) FAC |
| | |
| | 2)AN ENGINEER PRACTICING THROUGH A DULYAUTHORIZED |
| | ENGINEERING BUSINESS SHALL INDICATE THEIR NAME AND |
| | LICENSE #, AS WELL AS THE NAME,ADDRESS AND CERTIFICATE |
| | OF AUTHORIZATION #ON EACH SHEET PER |
| | 61G15-23.002 (2) FAC |
| | |
| | NOTE: TITLE BLOCK IS MISSING PE LICENSE NUMBER AND |
| | SHOWSCERTIFICATE OF AUTHORIZATION NUMBER AS THE |
| | LICENSE NUMBER PLEASE MAKE CORRECTIONS TO TITLE |
| | BLOCKS. |
| | |
| | 3)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS |
| | LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS |
| | AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST |
| | EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC |
| | (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES |
| | PER 108.3 FBC* FEES ARE DUE IN THE AMOUNT OF $164.63 |
| | FOR THE INCREASED VALUE. |
| | |
| | 4)SUBMIT TWO COPIES OF ENERGY CALC'S PER 13-101.2.2 |
| | FBC. BE SURE THAT THEY ARE SIGNED AND |
| | DATED BY PREPARER AND OWNER/AGENT PRIOR |
| | TO SUBMITTAL |
| | |
| | 5)IN AN EXISTING BUILDING WHERE ALTERATIONS ARE BEING |
| | MADE A DESIGN PROFESSIONAL MUST ELECT THE LEVEL OF |
| | ALTERATION PER 301.5 OF EXISTING BUILDING CODE AND |
| | STATE ALONG WITH THE TYPE OF CONSTRUCTION ON THE |
| | DRAWINGS |
| | |
| | 6)PROVIDE SEPARATION/BARRIER BETWEEN EXISTING WOOD |
| | BEAM AND NEW CONCRETE BEAM. |
| | |
| | 7)PROVIDE A KEY PLAN THAT NUMBERS OPENINGS FOR |
| | SHUTTERS AND A COMPLETED INSTALLATION SCHEDULE (SEE |
| | EXAMPLE ATTACHED) |
| | |
| | 8)PROVIDE PRODUCT APPROVALS FOR GLASS BLOCK AND |
| | SIMPSON CONNECTORS |
| | |
| | 9)IF EXISTING ROOF STRUCTURE STAYS IN PLACE ABOVE |
| | FRAMED WALL (SHORING WHILE WALLS ARE REPLACED) SHOW |
| | DETAIL FOR SUPPORT OF THE EXISTING WOOD BEAM AT IE. |
| | COLUMN AT THAT LOCATION AND DETAIL ON THE NEW TIE BEAM |
| | FROM THAT POINT ON AND THE METHOD TO TIE INTO EXISTING |
| | WALL. ALSO SHOW DROP DOWN ABOVE DOOR. |
| | |
| | 10)EMERGENCY EGRESS PER R310 FBC: |
| | MIN. NET CLEAR OPENING OF 5 SQ.FT. ON |
| | GRADE FLOOR. MIN. NET CLEAR OPENING ALL |
| | OTHER FLOORS OF 5.7 SQ.FT. IN BOTH CASES |
| | THE MIN.NET CLEAR HEIGHT SHALL BE 24" |
| | AND THE NET CLEAR WIDTH SHALL BE 20" WITH THE SILL |
| | HEIGHT NO MORE THAN 44" ABOVE FLOOR LEVEL TYPICALLY THE |
| | SH24 DOES NOT MEET THIS CRITERIA. |
| | |
| | 11)A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT IS REQUIRED PRIOR TO |
| | A PERMIT BEING ISSUED |
| | |
| | BLDG PLAN REVIEW |
| | ADRIAN MORSE |
| | 561-805-6716 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |