Plan Review Notes
Plan Review Notes For Permit 07050517
Permit Number 07050517
Review Stop P
Sequence Number 1
Notes
Date Text
2007-06-11 10:05:56DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SHEET 6: PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4
 THE SUBMITTED SANITARY ISOMETRIC RISER DIAGRAM DOES NOT
 RELECT THE FLOOR PLAN AND IS NOT CODE COMPLIANT. PLEASE
 REFERENCE THE CORRECTED SANITARY ISOMETRIC RISER
 DIAGRAM THAT REFLECTS THE FLOOR PLAN AND IS CODE
 COMPLIANT ATTACHED TO THE PLUMBING COMMENTS FOR THE
 RESUBMITTAL.
  
 2. SHEET 6: THE FOLLOWING CORRECTIONS ARE REQUIRED FOR
 THE WASHING MACHINE PER FBC-2004 PLUMBING, SECTIONS (A)
 406.3 WASTE CONNECTIONS.THE TRAP AND FIXTURE DRAIN FOR
 AN AUTOMATIC CLOTHES WASHER SHALL BE A MINIMUM OF 2
 INCHES (51MM) IN DIAMETER. THE AUTOMATIC CLOTHES WASHER
 FIXTURE DRAIN SHALL CONNECT TO A BRANCH DRAIN OR
 DRAINAGE STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER. PLEASE CORRECT SIZING ON THE RESUBMITTAL.
  
 (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY
 TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS
 FOR RODDING. PLEASE INDICATE THE STANDPIPE FOR THE
 WASHING MACHINE ON THE RESUBMITTAL.
  
 (C) 708.7 MINIMUM SIZE. CLEANOUTS SHALL
 BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102MM)
 NOTE: CLEANOUT FOR THE WASHING MACHINE SHALL BE THREE
 INCH (3"). PLEASE INDICATE THIS ON THE RESUBMITTAL.
  
 (D) 708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS.
 NOTE: CLEANOUT FOR THE WASHING MACHINE TO BE LOCATED AT
 FOUR FEET ABOVE FINNISH FLOOR (4' A.F.F.). PLEASE
 INDICATE THIS ON THE RESUBMITTAL.
  
 3. SHEET 6: FBC-2004 CHAPTER 1,SECTION 106.3.4.2:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 4. NOTE: THE CODE CYCLES THAT THIS PROJECT WAS
 DESIGNED UNDER IS FBC-2004 W/ 2006 REVISIONS. PLEASE
 ADD TO NOTES FOR CLARITY IN THE FIELD. THE REVISION
 DATES INDICATED ON THE DRAWINGS DO NOT INDICATE
 COMPLIANCE WITH THE CURRENT CODES AND ARE CONFUSING AND
 SHOULD BE REMOVED FOR THE RESUBMITTAL.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721