| 2007-05-29 11:44:08 | |
| | |
| | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| | COMPLIANCE AND RESUBMIT FOR REVIEW. |
| | |
| | 1} PER 110.9 AND 110.10: OBTAIN THE |
| | AVAILABLE FAULT CURRENT AT THE UTILITY |
| | AND CALCULATE THE SAME AT THE EQUIPMENT. |
| | INDICATE THE AIC RATING FOR THE |
| | EQUIPMENT IS EQUAL TO OR GREATER THAN |
| | THE AVAILABLE FAULT. |
| | |
| | 2} THE EQUIPMENT GROUND BETWEEN THE METER AND PANEL ON |
| | THE RISER DIAGRAM CREATES A PARALLEL PATH TO GROUND |
| | WITH THE NEUTRAL AND MUST BE REMOVED. AN ISOLATED |
| | NEUTRAL AND EQUIPMENT GROUND ARE TO BE RAN FROM THE |
| | FIRST MEANS OF DISCONNECT. 250.6. |
| | |
| | 3} PROVIDE A PANEL SCHEDULE PER 408.4. PLEASE SEE NEW |
| | VERBAGE FOR 2005 NEC: "THE IDENTIFICATION SHALL INCLUDE |
| | SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE |
| | DISTINGUISHED FROM ALL OTHERS." |
| | |
| | 4} DUE TO THE PANEL LOCATION, A DISCONNECT IS REQUIRED |
| | PER 225.32. INDICATE LOCATION ON RISER. |
| | |
| | 5} PLEASE INDICATE THE CODE CYCLES THIS PROJECT WAS |
| | DESIGNED UNDER. 2004 FBC, 2005 NEC ETC. ADD TO NOTES |
| | FOR CLARITY IN THE FIELD.. THE REVISION DATES DO NOT |
| | INDICATE COMPLIANCE WITH THE CURRENT CODES AND SHOULD |
| | BE REMOVED. |
| | |
| | 6} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST |
| | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |