2007-05-29 11:44:08 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 2} THE EQUIPMENT GROUND BETWEEN THE METER AND PANEL ON
 THE RISER DIAGRAM CREATES A PARALLEL PATH TO GROUND
 WITH THE NEUTRAL AND MUST BE REMOVED. AN ISOLATED
 NEUTRAL AND EQUIPMENT GROUND ARE TO BE RAN FROM THE
 FIRST MEANS OF DISCONNECT. 250.6.
  
 3} PROVIDE A PANEL SCHEDULE PER 408.4. PLEASE SEE NEW
 VERBAGE FOR 2005 NEC: "THE IDENTIFICATION SHALL INCLUDE
 SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE
 DISTINGUISHED FROM ALL OTHERS."
  
 4} DUE TO THE PANEL LOCATION, A DISCONNECT IS REQUIRED
 PER 225.32. INDICATE LOCATION ON RISER.
  
 5} PLEASE INDICATE THE CODE CYCLES THIS PROJECT WAS
 DESIGNED UNDER. 2004 FBC, 2005 NEC ETC. ADD TO NOTES
 FOR CLARITY IN THE FIELD.. THE REVISION DATES DO NOT
 INDICATE COMPLIANCE WITH THE CURRENT CODES AND SHOULD
 BE REMOVED.
  
 6} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718