| 2007-05-21 15:58:57 | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | 1} THE FEED TO SUB PANEL "B" MUST CONTAIN A #10CU | | | EQUIPMENT GROUND PER 250.122. | | | | | | 2} EGRESS LIGHTING IS REQUIRED PER 210.70(A)(2)(B). | | | | | | 3} THE "DINING ROOM" CIRCUIT MUST BE A 20 AMP AS | | | INDICATED, BUT CANNOT BE ON WITH THE LIVING ROOM | | | RECEPTACLES. SEE 210.52(B). | | | | | | 4} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A) (1). | | | | | | 5} A RECEPTACLE IS REQUIRED AT THE REAR OF THE | | | RESIDENCE PER 210.52(E). | | | | | | 6} THE ENGINEER OF RECORD'S SEAL IS INDISCERNIBLE. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|