| Plan Review Notes For Permit 07050509 |
| Permit Number |
07050509 |
|
| Review Stop |
B |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2008-02-23 08:35:58 | BUILDING PLAN REVIEW | | | PERMIT: 07050509 | | | ADD: 515 N. FLAGLER DR. #20 FL | | | CONT: SHAKMAN HOSPITALITY | | | TEL: (561)750-8288 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: REVISION | | | ACTION: DENIED | | | | | | 1)SHEET A-6 THE GA FILE #FC5406 AND RC2601 IS FOR | | | WOOD JOISTS OR WOOD FRAME SYSTEMS. THE DETAIL #12 ON | | | SHEET A-6 SHOWS AN EXISTING CONCRETE FLOOR HOWEVER; THE | | | SYSTEM PROPOSED IS FOR WOOD FLOORS-CEILING SYSTEMS. | | | PROVIDE A UL FLOOR PENETRATION SYSTEM WITH THE DESIGN | | | NUMBER. | | | | | | 2)THE HOLES SHALL BE SEALED WITH CONCRETE; HOLES | | | SHALL BE CREATED IN THE EXISTING CONCRETE OPENING FOR | | | REBAR TO PREVENT THE CONCRETE FROM FALLING OUT. | | | | | | 3)712.4.1.2 THROUGH PENETRATIONS SHALL BE PROTECTED | | | BY AN APPROVED THROUGH-PENETRATION FIRE STOP SYSTEM | | | INSTALLED AND TESTED IN ACCORDANCE WITH ASTM E 814 OR | | | UL 1479, WITH A MINIMUM POSITIVE PRESSURE DIFFERENTIAL | | | OF 0.01 INCH (2.49 PA) OF WATER. THE SYSTEM SHALL HAVE | | | AN F RATING AND A T RATING OF NOT LESS THAN 1 HOUR BUT | | | NOT LESS THAN THE REQUIRED RATING OF THE FLOOR | | | PENETRATED. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | FAX (561) 805-6676 | | | [email protected] | | | | | | 1 |
|