| Notes |
| Date |
Text |
| 2008-03-04 19:35:19 | ** DENIEDREVIEW FOR REVISION #4** | | | | | | 1) NOTE: PLEASE SEE NEW LIGHTING ADDED TO BATHROOMS YET | | | THE LIGHTING PERFORMANCE CALCULATIONS WERE NOT UPDATED | | | PER 13-415.2.ABC.1.1, .1.2 | | | | | | 2) NOTE: PLEASE VERIFY LIGHTING CONTROLS FOR THESE NEW | | | FIXTURES PER 13-415.1.ABC.1.1 AND .1.3. | | | PLEASE SEE .1.3 FOR CONTROLS OF DECRETIVE/ACCENT | | | LIGHTING. | | | | | | | | | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY | | | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE | | | DO NOT HESITATE IN CONTACTING THIS OFFICE. | | | PLEASE SEE BELOW FOR CONTACT INFORMATION. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|