| Plan Review Notes For Permit 07050509 |
| Permit Number |
07050509 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-10-23 16:48:05 | *****UNSAT***** SEE *NEW COMMENT | | | | | | THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE | | | BEEN ADDRESSED.THE SUBMITTED FIRE ALARM PLANS HAVE | | | BEEN ADDED AS A PART OF THE MASTER PERMIT PLANS TO SHOW | | | THE INTENT AND/OR LAYOUT OF THE FIRE ALARM SYSTEM.THE | | | SPEC SHEETS ASSOCIATED WITH THE FIRE ALARM PLAN NOT | | | NEEDED AT THIS TIME. THEY WILL BE REQUIRED WHEN THE THE | | | FIRE ALARM CONTRACTOR SUBMITS THE FIRE ALARM PLANS | | | UNDER A SEPARATE PERMIT ONCE THE MASTER PERMIT HAS BEEN | | | ISSUED. | | | | | | *NEW COMMENT | | | | | | A.THE LIFE SAFETY PLAN SHEET (A-13) HAS IN ITS NOTE | | | REFERENCE TO SHEET E-2.2;HOWEVER THIS SHEET COULD NOT | | | BE LOCATED. | | | | | | | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE (ON THE PLANS) EACH ITEM WAS | | | ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|