Plan Review Notes
Plan Review Notes For Permit 07050509
Permit Number 07050509
Review Stop E
Sequence Number 2
Notes
Date Text
2007-09-22 09:49:262007-09-22 09:49:26
  
 ** DENIED 2ND REVIEW**
  
 ** PLEASE SEE THERE ARE SOME ITEMS FROM PREVIOUS REVIEW
 WHICH ARE STILL IN NEED OF ADDRESSING.
  
 1) NOTE: COMMENT # 1 FROM PREVIOUS REVIEW. ONLY SOME OF
 THESE CODES COULD BE FOUND ON THE ELECTRICAL PLANS.
 PLEASE ADJUST.
  
 ** PLEASE SEE THE CODES ON PLANS NEED TO BE CORRECTED
 TO THE LATEST CODES ADOPTED BY THE STATE AS OF DECEMBER
 8TH, 2006.
 PLEASE LIST THE FOLLOWING.
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70 (NEC) 2002 SHOWN.
 2003 NFPA-101
 2002 NFPA-72
  
 THIS IS REQUIRED AT A MINIMUM ON ARCHITECTURAL AND
 ELECTRICAL PLANS.
  
 2) NOTE: AS MENTIONED ON PREVIOUS REVIEW NOTE #2,
 PLEASE KNOW THE FIRE ALARM PLANS STILL BEING SUBMITTED
 WITH THE BASE BUILD OUT PLANS WILL BE REQUIRED UNDER A
 SEPARATE PERMIT.
 PLEASE KNOW THE PREVIOUS REVIEW COMMENT WITH RESPECT TO
 THE MINIMUM LOCATIONS AND LEVELS FOR FBC ADA NEED TO BE
 ON THE BASE BUILD OUT PLANS.
 PLEASE SEE THE MINIMUM LEVELS AND NOT QUOTING THE CODE
 SECTIONS PREVIOUSLY GIVEN SHOULD BE ON PLANS. THESE
 LOCATIONS AND LEVELS ARE IN FBC 11-4.28.1, .2, AND .3.
  
 3) NOTE: PLEASE SEE FBC 2004 W/2006 REVISIONS AND
 CHAPTER 13.
 PLEASE SEE ENERGY CALCULATIONS FROM FLA-COM ARE STILL
 BEING SUBMITTED. PLEASE SEE POSSIBLE NOTES FROM
 MECHANICAL REVIEWER FOR THIS AND METHODS. AS THIS SPACE
 IS APPARENTLY ALREADY CONDITIONED SPACE, THIS
 ELECTRICAL REVIEWER ONLY NEEDS THE LIGHTING PERFORMANCE
 CALCULATIONS AS SHOWN ON E-2.
 PLEASE SEE AS THERE ARE FOUR SETS OF ENERGY
 CALCULATIONS SUBMITTED THE LIGHTING DESIGN USE ON
 CALCULATIONS DOES NOT CORRELATE WITH THE LIGHTING
 DESIGN USE ON PLANS ON E-2.
 PLEASE ALSO SEE THE FIXTURE LEGEND FOR ALL FIXTURES ARE
 NOT COMPLETE AT THIS TIME.
 THERE IS A WATTAGE GIVEN FOR TRACK LIGHTING HOWEVER
 FIXTURE LEGEND DOES NOT INDICATE ANY TRACK. PLEASE
 COORDINATE AND COMPLETE.
 PLEASE VERIFY HOW ACCENT LIGHTING IS BEING CONTROLLED
 PER 13-415.1ABC.1.3.
 THE PLANS DO INDICATE A COMBINATION OF SEVERAL TYPES OF
 DEVICES, HOWEVER IT IS UNCLEAR HOW THE ACCENT LIGHTING
 ETC WHICH IS NOT PART OF THE NORMAL LIGHTING IN AREAS
 IS BEING CONTROLLED.
 PLEASE SEE 13-415.2.ABC.1.2 AS THE WATTAGE WHICH IS TO
 USED AND FIGURED FOR TRACK LIGHTING (LINE VOLTAGE
 @120V)IS TO BE THE FIXTURE WATTAGE @ THE NUMBER OF
 FIXTURES OR THE TOTAL LINEAR FT OF TRACK AT 30VA PER FT
 WHICH EVER IS GREATER.
 AS THE PLANS INDICTED, THE TOTAL LENGTH OF TRACK @ 30VA
 PER FT IS GREATER THAN THE FIXTURES AND WATTAGE OF
 THOSE FIXTURES THEREFORE THE 30VA PER FT BASED ON TRACK
 SHALL BE USED. PLEASE ADJUST THE CALCULATIONS.
  
 4) NOTE: PLEASE SEE THE VALUE FOR COMPLETE SCOPE OF
 WORK AS APPLIED WILL NEED TO BE REVISED SUBSTANTIALLY
 BASED ON THE COMMENT ABOVE (NOTE #3).
 THE PLANS WHICH HAS NOW INCLUDED WORK NOT ON ORIGINAL
 PLANS AND APPLICATIONS NEEDS TO BE REVISED. NO
 ADJUSTMENT WAS MADE, NO RESPONSE ETC?
 PLEASE SEE FBC 108.3 WHICH REQUIRES THE VALUE TO
 INCLUDE ALL LABOR, MATERIALS, DESIGN COST, EQUIPMENT
 ETC, EVEN IF ANY OR PART IS OWNER SUPPLIED.
  
 5) NOTE: PLEASE SEE THE RESPONSE TO PREVIOUS NOTE #9
 MENTIONS THE PANEL SCHEDULES ON PLANS ARE NOT REQUIRED
 TO MATCH HOWEVER PLEASE KNOW THIS AHJ DOES REQUIRE THE
 PANEL SCHEDULE WHICH ARE ON RECORD SETS OF PLANS TO
 CORRELATE WITH THE PLANS FOR ALL SPECIFIC ROOMS AND
 AREAS.
 THIS IS SOMETHING THAT CAN AND WILL NEED TO BE ADJUSTED
 AND REVISED BEFORE FINAL HOWEVER THE PLANS DO NEED TO
 BE SPECIFIC.
 THERE ARE NUMEROUS RESEARCH REQUESTS FOR RECORD SET OF
 PLANS FOR PANEL SCHEDULES/DIRECTORIES.THE 2005 CODE
 BECAME MORE DETAILED ALONG WITH SEVERAL SECTION
 MEETINGS WITH THE CODE PANELISTS WHICH THE INTENT OF
 THIS IS NOT ONLY THE ON-SITE PANEL DIRECTORY BUT ALSO
 RECORD SET(S) OF PLANS.
 PLEASE ADJUST ACCORDINGLY. MAY BE DONE BY ALPHA OR
 NUMERIC DESIGNATIONS AND AS MENTIONED ABOVE THIS MAY BE
 GONE OVER SO THAT PART OF THIS MAY BE DONE AT FINAL
 REVISED PLANS.
 FBC 106.1.2, 106.3.1,106.3.5.1.2, 110.1.2 ETC
 ADMINISTRATIVE CODE SECTIONS FOR ADDITIONAL INFORMATION
 REQUIRED.
 NEC 408.4, 240.4, 310.16, 220 ETC.
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THE PANEL SCHEDULES NEED TO BE SPECIFIC TO
 ALL ROOMS, AREAS AND CIRCUITING IN WHICH THEY FEED.
 PLEASE SEE THE NUMERICAL DESIGNATION AS SHOWN ON PLANS
 MAY BE USED FOR THE CIRCUITS ON PANEL SCHEDULE OR LABEL
 WITH NAME(S).
 PLEASE SEE THE FOLLOWING TEXT IS TAKEN DIRECTLY FROM
 THE NEC 408.4 AND IS ONLY ONE OF THE SECTIONS AS
 MENTIONED.
  
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANELBOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION..*
  
 (EXAMPLE LV1- (31) OFFICE 128/127 RECEPTS) OR
 WORDS/IDENTIFICATION TO THAT AFFECT.
  
 6) NOTE: AS REQUESTED ON NOTE #11 ON PREVIOUS REVIEW.
 PLEASE EXPAND ON THE CALCULATIONS.
 HOW WAS LOAD DETERMINED ON RECEPTACLES? (MIN NEC
 220.44, 220.14H)
 HOW WAS LOAD FIGURED FOR TRACK LIGHTING? (MIN VA PER FT
 BASED ON NEC 220.43)
 PLEASE EXPLAIN WHERE THE 65% DE-RATING FOR RECEPTACLES
 IS IN THE NEC.
 SOME OF THIS PREVIOUS NOTE WAS DONE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE A COMPLETE LOAD SUMMARY ON HOW LOADS
 WERE DERIVED FOR LIGHTING, TRACK LIGHTING, RECEPTACLES
 AND ALL EQUIPMENT.
 PLEASE INDICATE ALL CONTINUOUS LOADS AT 125%. PLEASE
 INDICATE ANY HEAT LOADS, LARGEST MOTORS ETC. PLEASE SEE
 NEC 220, 215.3, 230.42 ETC.
 FBC 106.1.2, 106.3.5.1.2
  
 7) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #12 WHICH
 REQUESTED FOR INFORMATION REGARDING THE ACCESS/EGRESS
 CONTROL DEVICES HOWEVER THE RESPONSE WAS TO SEE THE
 ARCHITECTURAL SHEETS FOR THIS INFORMATION. THIS
 INFORMATION COULD NOT BE READILY LOCATED AND AS THESE
 DEVICES ARE ELECTRICAL IN NATURE THESE ARE TO BE ON
 ELECTRICAL PLANS.
 PLEASE SEE THE ARCHITECT DOES GIVE RESPONSES TO OTHER
 TRADES WHEN THE NOTE MAY HAVE BEEN FROM OTHER TRADES
 HOWEVER NONE OF HIS RESPONSES GAVE ANY REFERENCE TO
 THIS ELECTRICAL NOTE.
 PLEASE PROVIDE INFORMATION.
 **PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE MORE INFORMATION FOR ACCESS CONTROL
 LOCKS AS NOTED ON PLANS. PLEASE SEE THE LIFE SAFETY
 CODE AND SHOW COMPLIANCE FOR FAIL SAFE OPERATION OF
 THESE LOCKS AND DEVICES WHICH SHALL NOT IMPEDE THE
 EGRESS UNDER NORMAL OR EMERGENCY CONDITIONS. PLEASE SEE
 NFPA-101 7.2.1.5, 7.2.1.6.2
  
 ** PLEASE SEE POSSIBLE COMMENTS FROM OTHER TRADES WHICH
 MAY AFFECT ELECTRICAL PLANS OR DESIGN.
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW.
  
 *** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS
 OR COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE.
 IF THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY
 WAY, NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR,
 PLEASE DO NOT HESITATE IN CONTACTING THIS OFFICE AND
 THIS REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-09-21 16:58:51 
  
  
 REVIEW TO CONTINUE ON 9/22