| Date |
Text |
| 2007-06-18 12:27:55 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. SHT A-3 TWO DRINKING FOUNTAINS ARE REQUIRED PER |
| | TABLE 403.1.PLEASE INDICATE THE LOCATION FOR THE |
| | DRINKING FOUNTAINS, AND SUBMIT A DETAIL SHOWING |
| | COMPLIANCE WITH 11-4.15 AND ALL SUBSECTIONS AS WELL AS |
| | SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO HAVE |
| | DIFFICULTY BENDING OR STOOPING. SECTION 106.1.1. |
| | |
| | 2. SHT A-7 ACCESSIBLE TOILET ROOMS. SHOW COMPLIANCE |
| | WITH THE FOLLOWING: |
| | ___FOR W/C'S: |
| | A. 11-4.16.5 FLUSH CONTROLS |
| | ___FOR URINALS: |
| | A. 11-4.18.3 CLEAR FLOOR SPACE |
| | B. 11-4.18.4 FLUSH CONTROLS |
| | ___FOR LAVS: |
| | A. 11-4.19.2 HEIGHT (DETAIL B INDICATES 35") |
| | B. 11-4.19.5 FAUCETS |
| | |
| | 3. SHT A-7 SPECIAL NOTES #5 PER SECTION 1210.2 WALLS |
| | WITHIN 2' OF WATER CLOSETS AND URINALS SHALL BE |
| | "SMOOTH, HARD & NONABSORBENT SURFACES". VINYL |
| | WALLCOVERING DOES NOT MEET THE "HARD" REQUIREMENT OF |
| | THIS SECTION. PLEASE SHOW COMPLIANCE. |
| | |
| | 4. SHT A-9 DETAIL #4. SHOW COMPLIANCE WITH THE |
| | FOLLOWING: |
| | A. 11-4.24.3 KNEE CLEARANCE |
| | B. 11-4.24.4 SINK DEPTH |
| | C. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD APPROACH |
| | REQUIRED MAX 19" UNDERNEATH THE SINK. NO CABINET DOORS |
| | ALLOWED IN CLEAR FLOOR SPACE). |
| | D. 11-4.24.6 EXPOSED PIPES & SURFACES |
| | E. 11-4.24.7 FAUCETS |
| | |
| | 5. SHTS P-1 & P-2 OFFSET FOR THE STORM RWL INDICATED ON |
| | SHTS A-2 & A-3 SHALL BE INDICATED ON THE PLUMBING FLOOR |
| | PLANS, AND SHALL BE INDICATED BY A STORM ISOMETRIC |
| | RISER DIAGRAM. SECTION 106.1.1. |
| | |
| | 6. SHTS P-1 & P-2 FLOOR DRAINS ARE NOT APPROVED |
| | INDIRECT WASTE RECEPTORS. EITHER A FLOOR SINK OR A HUB |
| | DRAIN WILL BE APPROVED PER SECTIONS 802.3 OR 802.3.2. |
| | PLEASE INDICATE THE PROPER I.W. RECEPTOR. |
| | |
| | 7. ALL P, M, E & FS SHEETS. THE CERTIFICATE OF |
| | AUTHORIZATION NUMBER FOR THE ENGINEERING COMPANY SHALL |
| | BE INDICATED IN THE TITLE BLOCK ON EACH SHEET PER FAC |
| | 61G15-23.002(2) & FS 471.025. PLEASE SHOW CA# ON EACH |
| | SHEET. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6713 |
| | E-MAIL [email protected] |